13.7.9.3
Settings
PID-6976-SETTINGS v1
Table 330:
TIMERSET Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
t
0.000 - 90000.000
s
0.001
0.000
Delay for settable timer n
13.7.9.4
Technical data
GUID-C6C98FE0-F559-45EE-B853-464516775417 v2
Table 331:
Number of TIMERSET instances
Logic block
Quantity with cycle time Range or Value
Accuracy
3 ms
8 ms
100 ms
TIMERSET
15
15
30
(0.000–90000.000) s
±0.5% ±10 ms
13.7.10
Exclusive OR function block XOR
IP11018-1 v2
M11477-3 v4
The exclusive OR function (XOR) is used to generate combinatory expressions
with boolean variables. XOR has two inputs and two outputs. One of the outputs is
inverted. The output signal OUT is 1 if the input signals are different and 0 if they
are the same.
Table 332:
Truth table for XOR function block
INPUT1
INPUT2
OUT
NOUT
0
0
0
1
0
1
1
0
1
0
1
0
1
1
0
1
13.7.10.1
Function block
M11476-3 v1
IEC04000409-2-en.vsd
XOR
INPUT1
INPUT2
OUT
NOUT
IEC04000409 V2 EN-US
Figure 264:
XOR function block
Section 13
1MRK 506 382-UEN A
Logic
502
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...