![ABB RELION 650 SERIES Technical Manual Download Page 513](http://html.mh-extra.com/html/abb/relion-650-series/relion-650-series_technical-manual_2122513.webp)
13.9.7
Operation principle
SEMOD175737-4 v5
The Boolean 16 to integer conversion function (B16I) will transfer a combination
of up to 16 binary inputs INx, where 1≤x≤16, to an integer. Each INx represents a
value according to the table below from 0 to 32768. This follows the general
formula: INx = 2
x-1
where 1≤x≤16. The sum of all the values on the activated INx
will be available on the output OUT as a sum of the integer values of all the inputs
INx that are activated. OUT is an integer. When all INx (where 1≤x≤16) are
activated, that is = Boolean 1, it corresponds to that integer 65535 is available on
the output OUT. The B16I function is designed for receiving up to 16 booleans
input locally. If the BLOCK input is activated, it will freeze the output at the last
value.
Values of each of the different OUTx from function block B16I for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the
output OUT on the function block B16I
Name of input
Type
Default
Description
Value when
activated
Value when
deactivated
IN1
BOOLEAN
0
Input 1
1
0
IN2
BOOLEAN
0
Input 2
2
0
IN3
BOOLEAN
0
Input 3
4
0
IN4
BOOLEAN
0
Input 4
8
0
IN5
BOOLEAN
0
Input 5
16
0
IN6
BOOLEAN
0
Input 6
32
0
IN7
BOOLEAN
0
Input 7
64
0
IN8
BOOLEAN
0
Input 8
128
0
IN9
BOOLEAN
0
Input 9
256
0
IN10
BOOLEAN
0
Input 10
512
0
IN11
BOOLEAN
0
Input 11
1024
0
IN12
BOOLEAN
0
Input 12
2048
0
IN13
BOOLEAN
0
Input 13
4096
0
IN14
BOOLEAN
0
Input 14
8192
0
IN15
BOOLEAN
0
Input 15
16384
0
IN16
BOOLEAN
0
Input 16
32768
0
The sum of the numbers in column “Value when activated” when all INx (where
1≤x≤16) are active that is=1; is 65535. 65535 is the highest boolean value that can
be converted to an integer by the B16I function block.
1MRK 506 382-UEN A
Section 13
Logic
Line distance protection REL650 2.2 IEC
507
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...