7.9.3
Function block
M17149-3 v6
CCPDSC
I3P*
BLOCK
BLKDBYAR
CLOSECMD
OPENCMD
EXTPDIND
POLE1OPN
POLE1CL
POLE2OPN
POLE2CL
POLE3OPN
POLE3CL
TRIP
START
IEC13000305-1-en.vsd
IEC13000305 V1 EN-US
Figure 117:
CCPDSC function block
7.9.4
Signals
PID-3525-INPUTSIGNALS v8
Table 127:
CCPDSC Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Three phase currents
BLOCK
BOOLEAN
0
Block of function
BLKDBYAR
BOOLEAN
0
Block of function at CB single phase auto re-
closing cycle
CLOSECMD
BOOLEAN
0
Close order to CB
OPENCMD
BOOLEAN
0
Open order to CB
EXTPDIND
BOOLEAN
0
Pole discordance signal from CB logic
POLE1OPN
BOOLEAN
1
Pole one opened indication from CB
POLE1CL
BOOLEAN
0
Pole one closed indication from CB
POLE2OPN
BOOLEAN
1
Pole two opened indication from CB
POLE2CL
BOOLEAN
0
Pole two closed indication from CB
POLE3OPN
BOOLEAN
1
Pole three opened indication from CB
POLE3CL
BOOLEAN
0
Pole three closed indication from CB
PID-3525-OUTPUTSIGNALS v8
Table 128:
CCPDSC Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip signal to CB
START
BOOLEAN
Trip condition TRUE, waiting for time delay
Section 7
1MRK 506 382-UEN A
Current protection
246
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...