Name
Values (Range)
Unit
Step
Default
Description
ZoneSeqCoord
Off
On
-
-
Off
Coordination of down stream devices to
local protection unit’s AR
tSuccessful
0.000 - 60.000
s
0.001
1.000
Delay time before indicating successful
reclosing
tSlaveDeadTime
0.100 - 60.000
s
0.001
0.400
Wait time for the slave to close when
WAIT input has reset
11.2.6
Operation principle
11.2.6.1
Terminology explanation
GUID-EA0760DF-8F0B-4146-8A42-3F20E75E1053 v1
Before describing the auto reclosing function it is first necessary to define the
following terminology:
•
a
shot
is an attempt from the function to close a circuit breaker
•
multi-shot
is where more than one shot is attempted
•
dead time
is the time between a start of the function and the attempt to close
the circuit breaker
•
reclaim time
is the time from the circuit breaker closing command till the
reset of the function, should the auto reclosing attempt be successful and no
new start is received
•
high-speed
shot is generally used for an application where the dead time is
less than 1 second and synchrocheck is not required
•
delayed
auto reclosing is generally regarded as an application where the dead
time is greater than 1 second and where typically synchrocheck is required
•
sequence
is the auto reclosing cycle beginning with start and ending with
successful, unsuccessful or aborted reclosing as a result
•
status
is the state which the auto reclosing function have reached in the
sequence
11.2.6.2
Status descriptions
GUID-AFC069D6-ADA5-4D97-9699-8C9F058458EB v1
The auto reclosing function can be in one of the following five statuses:
“Inactive”
GUID-BF80C969-FCBE-4CAB-BF71-9590A2DB433C v1
The auto recloser is in “inactive” status when the following conditions are fulfilled:
•
the auto recloser is set to
On
and
•
either the circuit breaker is not closed
•
or the circuit breaker is not ready
The function will not react on any start from protection trips while in
“inactive” status and no automatic reclosing is possible.
Section 11
1MRK 506 382-UEN A
Control
358
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...