Data Value
Data Valid
Comm Valid
Test
Receiver in test mode and incoming
data with q= Normal
Updated
1
1
0
Receiver in test mode and incoming
data with q= Test
Updated
1
1
1
Communication Error
0
0
0
0
The input of this GOOSE block must be linked either in SMT by
means of a cross or in ACT by means of a GOOSE connection (if
easy GOOSE engineering is enabled) to receive the double point
values.
The implementation for IEC 61850 quality data handling is
restricted to a simple level. If quality data validity is GOOD then
the DATAVALID output will be HIGH. If quality data validity is
INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD
DATA then the DATAVALID output will be LOW.
17.4.8
GOOSE function block to receive an integer value
GOOSEINTRCV
17.4.8.1
Identification
GUID-93A1E81B-1DE8-483A-BB3B-DB771EE66DC1 v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
GOOSE function block to receive an
integer value
GOOSEINTRCV
-
-
17.4.8.2
Functionality
GUID-27B1ED7A-C8E8-499E-89C1-C656FB0337F8 v3
GOOSEINTRCV is used to receive an integer value using IEC 61850 protocol via
GOOSE.
17.4.8.3
Function block
GUID-56F0C9F7-98F3-4091-B071-53CA5074DC8F v1
IEC10000250-2-en.vsd
GOOSEINTRCV
BLOCK
^SRCINTOUT
^INTOUT
DATAVALID
COMMVALID
TEST
IEC10000250 V2 EN-US
Figure 345:
GOOSEINTRCV function block
1MRK 506 382-UEN A
Section 17
Station communication
Line distance protection REL650 2.2 IEC
681
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...