17.8.2.3
Function block
GUID-EC5F1C83-0F47-4548-86E3-FFE056571241 v2
IEC10000287-1-en.vsd
I103MEAS
BLOCK
IL1
IL2
IL3
IN
UL1
UL2
UL3
UL1L2
UN
P
Q
F
IEC10000287 V1 EN-US
Figure 361:
I103MEAS function block
17.8.2.4
Signals
PID-6625-INPUTSIGNALS v4
Table 525:
I103MEAS Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of service value reporting
IL1
REAL
0.0
Service value for current phase L1
IL2
REAL
0.0
Service value for current phase L2
IL3
REAL
0.0
Service value for current phase L3
IN
REAL
0.0
Service value for residual current IN
UL1
REAL
0.0
Service value for voltage phase L1
UL2
REAL
0.0
Service value for voltage phase L2
UL3
REAL
0.0
Service value for voltage phase L3
UL1L2
REAL
0.0
Service value for voltage phase-phase L1-L2
UN
REAL
0.0
Service value for residual voltage UN
P
REAL
0.0
Service value for active power
Q
REAL
0.0
Service value for reactive power
F
REAL
0.0
Service value for system frequency
17.8.2.5
Settings
PID-6625-SETTINGS v4
Table 526:
I103MEAS Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
MaxIL1
1 - 99999
A
1
3000
Maximum current phase L1
MaxIL2
1 - 99999
A
1
3000
Maximum current phase L2
MaxIL3
1 - 99999
A
1
3000
Maximum current phase L3
Table continues on next page
1MRK 506 382-UEN A
Section 17
Station communication
Line distance protection REL650 2.2 IEC
739
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...