StartPhSel
1 out of 3
2 out of 3
3 out of 3
-
-
1 out of 3
Number of phases required for op (1 of
3, 2 of 3, 3 of 3)
DirMode1
Off
Non-directional
Forward
Reverse
-
-
Non-directional
Directional mode of step 1 (off, nodir,
forward, reverse)
Characterist1
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
-
-
ANSI Def. Time
Selection of time delay curve type for
step 1
I1>
5 - 2500
%IB
1
1000
Operating phase current level for step 1
in % of IBase
t1
0.000 - 60.000
s
0.001
0.000
Def time delay or add time delay for
inverse char of step 1
k1
0.05 - 999.00
-
0.01
0.05
Time multiplier for the inverse time delay
for step 1
IMin1
1 - 10000
%IB
1
100
Minimum operate current for step1 in %
of IBase
t1Min
0.000 - 60.000
s
0.001
0.000
Minimum operate time for inverse curves
for step 1
I1Mult
1.0 - 10.0
-
0.1
2.0
Multiplier for current operate level for
step 1
DirMode2
Off
Non-directional
Forward
Reverse
-
-
Non-directional
Directional mode of step 2 (off, nodir,
forward, reverse)
Table continues on next page
Section 7
1MRK 506 382-UEN A
Current protection
166
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...