![ABB RELION 650 SERIES Technical Manual Download Page 129](http://html.mh-extra.com/html/abb/relion-650-series/relion-650-series_technical-manual_2122129.webp)
Name
Type
Default
Description
BLKI01
BOOLEAN
0
Block inhibit of start output for slow swing
condition
BLKI02
BOOLEAN
0
Block inhibit of start output for subsequent
residual current detection
BLK1PH
BOOLEAN
0
Block one-out-of-three-phase operating mode
REL1PH
BOOLEAN
0
Release one-out-of-three-phase operating mode
BLK2PH
BOOLEAN
0
Block two-out-of-three-phase operating mode
REL2PH
BOOLEAN
0
Release two-out-of-three-phase operating mode
I0CHECK
BOOLEAN
0
Residual current (3I0) detection used to inhibit
start output
TRSP
BOOLEAN
0
Single-pole tripping command issued by tripping
function
EXTERNAL
BOOLEAN
0
Input for external detection of power swing
PID-3663-OUTPUTSIGNALS v6
Table 39:
ZMRPSB Output signals
Name
Type
Description
START
BOOLEAN
Power swing detected
ZOUT
BOOLEAN
Measured impedance within outer impedance
boundary
ZIN
BOOLEAN
Measured impedance within inner impedance
boundary
6.2.5
Settings
PID-3663-SETTINGS v6
Table 40:
ZMRPSB Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Mode On / Off
X1InFw
0.01 - 3000.00
Ohm/p
0.01
30.00
Inner reactive boundary, forward
R1LIn
0.01 - 1000.00
Ohm/p
0.01
30.00
Line resistance for inner characteristic
angle
R1FInFw
0.01 - 1000.00
Ohm/l
0.01
30.00
Fault resistance coverage to inner
resistive line, forward
X1InRv
0.01 - 3000.00
Ohm/p
0.01
30.00
Inner reactive boundary, reverse
R1FInRv
0.01 - 1000.00
Ohm/l
0.01
30.00
Fault resistance line to inner resistive
boundary, reverse
OperationLdCh
Off
On
-
-
On
Operation of load discrimination
characteristic
RLdOutFw
0.01 - 3000.00
Ohm/p
0.01
30.00
Outer resistive load boundary, forward
ArgLd
5 - 70
Deg
1
25
Load angle determining load impedance
area
RLdOutRv
0.01 - 3000.00
Ohm/p
0.01
30.00
Outer resistive load boundary, reverse
Table continues on next page
1MRK 506 382-UEN A
Section 6
Impedance protection
Line distance protection REL650 2.2 IEC
123
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...