6.5.6.4
Output
GUID-FCDCF1A9-A34D-4FD7-B488-3F31A93BE231 v1
All loop releasing signals are gathered in the binary coded integer output ZREL.
The value of ZREL can be calculated according to Equation
.
32
*
1
3
16
*
3
2
8
*
2
1
4
*
3
2
*
2
1
*
1
L
L
L
L
L
L
N
L
N
L
N
L
ZREL
IECEQUATION16018 V1 EN-US
(Equation 15)
For example, if only L1N is active, then the value is 1. If both start L1N and L3N
are active, then the value is 1+4=5.
The phase-to-phase loops are always released, that is, the value of
ZREL will always be at least 8+16+32=56. For example:
If only L1N is active, then the value is 1+56=57
If start L1N and L3N are active, then the value is 1+4+56=61
The BLOCK input will only block the enabling signals for phase-
to-earth loops, phase-to-phase loops are still released. The
PPL2PHIZ is designed not to have any influence on the phase-to-
phase loops of the distance protection.
BLOCK
TRUE
Bool to
Integer
ZREL
L3L1
L2L3
L1L2
L3N
L2N
L1N
zrelL1
zrelL2
zrelL3
TRUE
TRUE
startU
AND
AND
AND
AND
IEC16000025-1-en.vsdx
IEC16000025 V1 EN-US
Figure 78:
Output
Section 6
1MRK 506 382-UEN A
Impedance protection
156
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...