This undervoltage functionality together with additional ACT logic can be used to
provide functionality for overcurrent protection with undervoltage seal-in.
7.10.8
Technical data
GUID-7EA9731A-8D56-4689-9072-D72D9CDFD795 v8
Table 139:
VRPVOC technical data
Function
Range or value
Accuracy
Start overcurrent
(2.0 - 5000.0)% of IBase
±1.0% of I
r
at I ≤ I
r
±1.0% of I at I > I
r
Reset ratio, overcurrent
> 95%
-
Operate time, start overcurrent at 0 to 2 x I
set
Min. = 15 ms
-
Max. = 30 ms
Reset time, start overcurrent at 2 x I
set
to 0
Min. = 15 ms
-
Max. = 30 ms
Operate time, start overcurrent at 0 to 10 x
I
set
Min. = 5 ms
Max. = 20 ms
-
Reset time, start overcurrent at 10 x I
set
to 0
Min. = 20 ms
Max. = 35 ms
-
Independent time delay to operate at 0 to 2 x
I
set
(0.00 - 6000.00) s
±0.2% or ±35 ms
whichever is
greater
Inverse time characteristics,
and
13 curve types
See tables
Minimum operate time for inverse time
characteristics
(0.00 - 60.00) s
±0.2% or ±35 ms
whichever is
greater
High voltage limit, voltage dependent
operation
(30.0 - 100.0)% of UBase
±1.0% of U
r
Start undervoltage
(2.0 - 100.0)% of UBase
±0.5% of U
r
Reset ratio, undervoltage
< 105%
-
Operate time start undervoltage at 2 x U
set
to
0
Min. = 15 ms
-
Max. = 30 ms
Reset time start undervoltage at 0 to 2 x U
set
Min. = 15 ms
-
Max. = 30 ms
Independent time delay to operate,
undervoltage at 2 x U
set
to 0
(0.00 - 6000.00) s
±0.2% or ±35 ms
whichever is
greater
Internal low voltage blocking
(0.0 - 5.0)% of UBase
±0.25% of U
r
Overcurrent:
Critical impulse time
Impulse margin time
10 ms typically at 0 to 2 x I
set
15 ms typically
-
Undervoltage:
Critical impulse time
Impulse margin time
10ms typically at 2 x U
set
to 0
15 ms typically
-
1MRK 506 382-UEN A
Section 7
Current protection
Line distance protection REL650 2.2 IEC
257
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...