desired position within the two time limits
tStartMove
and
tIntermediate
. The
default values for
tStartMove
and
tIntermediate
are for a breaker. The typical
values for a disconnector are:
•
tStartMove
= 3s
•
tIntermediate
= 15s
In most cases,
tStartMove
and
tIntermediate
can be set to the same
values as in the source XCBR function. However, if the time limits
are set very close to the actual movement times of the apparatus,
compensation may be needed for the communication delays and
differences in cycle time of the XLNPROXY function and the
source function. The compensation should be in the range of 0 -
5ms.
When the switch has started moving, it issues a response to the SCSWI function
that the operation has started. If it does not start moving within
tStartMove
, the
command is deemed as failed, and a cause is raised on the L_CAUSE output and
sent to the SCSWI. The different causes it can identify are listed in order of priority
in table 1. The detection of the different ways of blocking is done while waiting for
movement of the switch, but the cause is not given until the
tStartMove
has
elapsed.
Table 229:
Possible cause values from XLNPROXY
Cause
No
Cause Description
Conditions
8
Blocked-by-Mode
The BEH input is 5.
2
Blocked-by-switching-hierarchy
The LOC input indicates that only local commands are
allowed for the breaker IED function.
-24
Blocked-for-open-cmd
The BLKOPN is active indicating that the switch is
blocked for open commands.
-25
Blocked-for-close-cmd
The BLKCLS is active indicating that the switch is
blocked for close commands.
9
Blocked-by-process
If the Blk input is connected and active indicating that the
switch is dynamically blocked. Or if the OPCAP input is
connected, it indicates that the operation capability of the
switch is not enough to perform the command.
5
Position-reached
Switch is already in the intended position.
-31
Switch-not-start-moving
Switch did not start moving within tStartMove.
-32
Persistent-intermediate-state
The switch stopped in intermediate state for longer than
tIntermediate.
-33
Switch-returned-to-init-pos
Switch returned to the initial position.
-34
Switch-in-bad-state
Switch is in a bad position.
-35
Not-expected-final-position
Switch did not reach the expected final position.
The L_CAUSE output keeps its output value until a new command sequence has
been started.
1MRK 506 382-UEN A
Section 11
Control
Line distance protection REL650 2.2 IEC
413
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...