Instruction Leaflet 

IL29C092E

Installation Instructions for KD, HKD, KDC, CKD,

CHKD, Circuit Breakers with Digitrip OPTIM 

Trip Unit and Powernet and/or Zone Interlock

Summary of Contents for CHKD

Page 1: ...anual Operation 7 4 Inspection and Field Testing 7 Effective November 2013 Supersedes IL29C092D 08 11 Instruction Leaflet IL29C092E Installation Instructions for KD HKD KDC CKD CHKD Circuit Breakers w...

Page 2: ...dations Electrotechnical Commision Recommendations No warnings and cautions relating to the safety of person IEC 157 1 The OPTlM 750 and 1050 K Frame circuit nel and equipment as well as all general a...

Page 3: ...CAUTION WHEN REMOVED AND REINSTALLED THREAD FORMING SCREWS WILL TRY TO REFORM THE THREADS IN THE BASE CARE SHOULD BE TAKEN EVERY TIME A THREAD FORIVIING SCREW IS USEDTO ENSURE THE SCREW STARTS IN THE...

Page 4: ...crew Terminal Mounting Screw Figure 2 1 Terminal lnstallation 2 3 Pole Breakers 4 Pole Breaker Circuit Figure 2 2 Circuit Breaker Mounting Bolt Drilling Plans Circuit Breaker Handle Figure 2 3 Circuit...

Page 5: ...iring connections are made on the removable male plug of the terminal block 4 If the customer requires the interlock feature in their system then the removal of the jumper between positions 2 3 is req...

Page 6: ...RSONAL INJURY MAIN TAIN ORIGINAL ELECTRICAL CLEARANCE AND CREEPAGE SPACINGS AT TERMINATIONS 2 12 Connect the control wires and power wires to their appropriate locations on the male plug of the termin...

Page 7: ...oes not affect the operation of the circuit breaker itself No circuit breaker should be reclosed until the cause of trip is known and the situation rectified PUSH TO TRIP Button The PUSH TO TRIP butto...

Page 8: ...ult Trip Units Code Requirements The National Electrical Code under Article 230 95 C requires that any ground fault protection system be per formance tested when first installed The test shall be cond...

Page 9: ...AUTION GROUND FAULT TEST RECORD FORM Ground Fault Test Records should be Retained by Those in Charge of the Building s FIELD TESTING SHOULD BE USED FOR FUNCTION AL TESTING AND NOT FIELD CALIBRATION OF...

Page 10: ...n Leaflet IL29C092E Effective November 2013 Installation Instructions for KD HKD KDC CKD CHKD Circuit Breakers with Digitrip OPTIM Trip Unit and Powernet and or Zone Interlock EATON CORPORATION www ea...

Page 11: ...n Leaflet IL29C092E Effective November 2013 Installation Instructions for KD HKD KDC CKD CHKD Circuit Breakers with Digitrip OPTIM Trip Unit and Powernet and or Zone Interlock EATON CORPORATION www ea...