6
Instruction Leaflet
IL29C092E
Effective November 2013
Installation Instructions for KD, HKD, KDC, CKD
CHKD, Circuit Breakers with Digitrip OPTIM
Trip Unit and Powernet and/or Zone Interlock
EATON CORPORATION
www.eaton.com
Table 2-1 Terminal Types
Terminal Terminal Screw
AWG
Wire
Torque
Cat.
No.
Material
Head
Wire
Wire
Type
Value
Body
Type
Range
Range
Ib-in
Aluminum Socket
35-185
275 (31)
Aluminum Socket
120-240
375 (42)
Socket
275 (31)
K Aluminum Socket
275 375
or
or
(31
375 (42)
Socket
240-300
550 (62)
Socket
35-185 Cu Only 275 (31)
Copper
Socket
120-240
375 (42)
Copper
Socket
Cu Only 275 (31)
CAUTION
WHEN ALUMINUM CONDUCTORS ARE USED, THE
APPLICATION OF A SUITABLE JOINT COMPOUND
IS RECOMMENDED TO REDUCE THE POSSIBILITY
OF TERMINAL OVERHEATING. OVERHEATING
CAN CAUSE NUISANCE TRIPPING AND DAMAGE
TO THE CIRCUIT BREAKER.
Table
2-2
Rating Plugs
2-11. When step-type terminals (TA400K, TA401K,
TA402K or T400K) are used, terminal shields (supplied
with terminals) must be installed on the circuit breaker
(Figure 2-4). Warning label supplied with the kit must
be attached to the circuit breaker cover.
WARNING
HAZARDOUS VOLTAGE CONDITIONS CAN CAUSE
DEATH OR SEVERE PERSONAL INJURY. MAIN-
TAIN ORIGINAL ELECTRICAL CLEARANCE AND
CREEPAGE SPACINGS AT TERMINATIONS.
2-12. Connect the control wires and power wires to their
appropriate locations on the male plug of the terminal
block, see Figure 2-5. Control power is necessary if
IMPACC communication is required.
2-13. Install an appropriate rating plug, see Table 2-2.
2-14. Plug in the hand held Digitrip OPTIMIZER into the
programming port and set the INCOM address. Then
set the various trip unit current settings using the OPTI-
MIZER, or when INCOM is available, use the circuit
Connect line and load conductors and accessory
leads.
When a dual conductor terminal (Catalog
No.
TA402K, TA401K, TA400K or T400K is installed on
the circuit breaker and
a single conductor is used,
the conductor should be installed in the terminal
opening nearest to the circuit breaker terminal
mounting conductor.
2-8. Install the supplied neutral current sensor in the
neutral pole of a four-wire system, see Figure 2-6.
2-9. After the circuit breaker is installed, check all
mounting hardware and terminal connecting hardware
for correct torque loading. Torque values for line/load
terminals are given in Table 2-1 and on the circuit
breaker nameplate.
2-1 0. If required, install line terminal cover on circuit
breaker cover with mounting slots provided.
13
tapped
Figure
2-6
Neutral Sensor Dimensions