![ABB RELION 650 SERIES Technical Manual Download Page 109](http://html.mh-extra.com/html/abb/relion-650-series/relion-650-series_technical-manual_2122109.webp)
The plain Mho circle has the characteristic as in figure
deriving the angle β is according to equation
β =
−
(
)
−
(
)
⋅
arg
arg
U
I
Z
U
L L
L L
set
pol
1 2
1 2
1
IECEQUATION15027 V1 EN-US
(Equation 3)
where
U
L1L2
EQUATION1790 V2
EN-US
is the voltage vector difference between phases L1 and L2
I
L1L2
EQUATION1791 V2
EN-US
is the current vector difference between phases L1 and L2
Z
set
1
is the positive sequence impedance setting for phase-to-phase fault in zone direction
For Zone 1,
Z
R PPZ
j X PPZ
set
1
1
1
1
1
=
+ ⋅
IECEQUATION15011 V1 EN-US
(Equation 4)
where
R1PPZ1
is the positive sequence resistive reach for phase-to-phase fault for zone 1
X1PPZ1
is the positive sequence reactance reach for phase-to-phase fault for zone 1
For Zone 2-5 and RV
Z
R Zx
j X Zx
set
1
1
1
=
+ ⋅
IECEQUATION15012 V1 EN-US
(Equation 5)
where
R1Zx
is the positive sequence resistive reach for zone x (x=2-5 and RV)
X1Zx
is the positive sequence reactance reach for zone x (x=2-5 and RV)
U
pol
is the polarizing voltage
Operation occurs if 90°≤β≤270°
1MRK 506 382-UEN A
Section 6
Impedance protection
Line distance protection REL650 2.2 IEC
103
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...