![ABB RELION 650 SERIES Technical Manual Download Page 124](http://html.mh-extra.com/html/abb/relion-650-series/relion-650-series_technical-manual_2122124.webp)
In addition to the normal cyclic reporting the IED also report spontaneously when
measured value passes any of the defined threshold limits.
IEC05000500-2-en.vsdx
V
a
lu
e
1
Y
t
V
a
lu
e
2
V
a
lu
e
3
V
a
lu
e
4
Value Reported
(1st)
Value Reported
V
a
lu
e
5
Value Reported
Y1
Y2
Y5
Value Reported
Value Reported
Y3
Y4
(*)Set value for t: XDbRepInt
t (*)
t (*)
t (*)
t (*)
IEC05000500 V2 EN-US
Figure 50:
Periodic reporting
Amplitude dead-band supervision
SEMOD54417-163 v6
If a measuring value is changed, compared to the last reported value, and the
change is larger than the ±ΔY pre-defined limits that are set by user (
XDbRepInt
),
then the measuring channel reports the new value to a higher level. This limits the
information flow to a minimum necessary. Figure
shows an example with the
amplitude dead-band supervision. The picture is simplified: the process is not
continuous but the values are evaluated with a time interval of one execution cycle
from each other.
Section 6
1MRK 506 382-UEN A
Impedance protection
118
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...