S
R
SR
Q
OR
AND
AND
30 ms
t
150 ms
START
STL1
OR
BackupTrip L1
BFP Started L1
Reset L1
BLOCK
Retrip Time Out L1
IEC09000976-2-en.vsd
Time out L1
IEC09000976 V2 EN-US
Figure 113:
Simplified logic scheme of the CCRBRF starting logic
AND
AND
AND
AND
AND
OR
OR
OR
a
b
a>b
AND
a
b
a>b
I>BlkCont
AND
Time out L1
BFP Started L1
Reset L1
CBCLDL1
Current High L1
Contact Closed L1
IEC09000977-2-en.vsd
FunctionMode
OR
OR
Current
Contact
Current and Contact
1
IP>
CB Closed L1
IL1
IEC09000977 V2 EN-US
Figure 114:
Simplified logic scheme of the CCRBRF , CB position evaluation
t
t1
tPulse
AND
AND
OR
OR
OR
TRRETL3
TRRETL2
BFP Started L1
Retrip Time Out L1
CB Closed L1
TRRET
TRRETL1
CBFLT
CB Pos Check
No CBPos Check
OR
From other
phases
IEC09000978-4-en.vsd
RetripMode
1
30ms
IEC09000978 V4 EN-US
Figure 115:
Simplified logic scheme of the retrip logic function
1MRK 506 382-UEN A
Section 7
Current protection
Line distance protection REL650 2.2 IEC
243
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...