The default value of
AngleRCA
is –55°. The parameter
AngleROA
gives the
angular distance from
AngleRCA
to define the directional borders.
A minimum current for the directional phase start current signal can be set.
IMinOpPhSel
is the start level for the directional evaluation of IL1, IL2 and IL3.
The directional signals release the overcurrent measurement in the respective
phases if their current amplitudes are higher than the start level (
IMinOpPhSel
) and
the direction of the current is according to the set direction of the step.
If no blocking signals are active, the start signal will start the timer of the steps.
The time characteristic for each step can be chosen as definite time delay or an
inverse time delay characteristic. A wide range of standardized inverse time delay
characteristics is available. It is also possible to create a tailor made time
characteristic.
The possibilities for inverse time characteristics are described in section
.
a
b
a>b
OR
|I
OP
|
STx
TRx
AND
Ix>
BLKSTx
BLOCK
Characteristx=DefTime
DirModex=Off
DirModex=Non-directional
DirModex=Forward
DirModex=Reverse
AND
AND
FORWARD_Int
REVERSE_Int
OR
OR
STAGEx_DIR_Int
IEC12000008.vsd
AND
AND
Characteristx=Inverse
Inverse
tx
min
tx
IEC12000008.vsd
IEC12000008 V2 EN-US
Figure 84:
Simplified logic diagram for OC4PTOC
1MRK 506 382-UEN A
Section 7
Current protection
Line distance protection REL650 2.2 IEC
175
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...