permissive tripping at the local end. This blocking condition is maintained long
enough to ensure that no unwanted operation will occur as a result of the current
reversal.
On verification of a weak end infeed condition, the weak end infeed logic provides
an output for sending the received teleprotection signal back to the remote sending
end and other output(s) for local tripping. For terminals equipped for single- and
two-pole tripping, outputs for the faulted phase(s) are provided. Undervoltage
detectors are used to detect the faulted phase(s).
12.2.3
Function block
SEMOD53507-9 v6
IEC06000287-2-en.vsd
ZCRWPSCH
U3P*
BLOCK
IRVBLK
IRV
WEIBLK1
WEIBLK2
VTSZ
CBOPEN
CRL
IRVL
TRWEI
TRWEIL1
TRWEIL2
TRWEIL3
ECHO
IEC06000287 V2 EN-US
Figure 224:
ZCRWPSCH function block
12.2.4
Signals
PID-3521-INPUTSIGNALS v8
Table 255:
ZCRWPSCH Input signals
Name
Type
Default
Description
U3P
GROUP
SIGNAL
-
Group signal for voltage input
BLOCK
BOOLEAN
0
Block of function
IRVBLK
BOOLEAN
0
Block of current reversal function
IRV
BOOLEAN
0
Activation of current reversal logic
WEIBLK1
BOOLEAN
0
Block of WEI logic
WEIBLK2
BOOLEAN
0
Block of WEI logic due to operation of other
protections
VTSZ
BOOLEAN
0
Block of trip from WEI logic through fuse-failure
function
CBOPEN
BOOLEAN
0
Block of trip from WEI logic by an open breaker
CRL
BOOLEAN
0
POR Carrier receive for WEI logic
Section 12
1MRK 506 382-UEN A
Scheme communication
442
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...