Name
Values (Range)
Unit
Step
Default
Description
tBCrv1
0.00 - 20.00
-
0.01
0.00
Param B for customized inverse trip time
curve for step 1
tCCrv1
0.1 - 10.0
-
0.1
1.0
Param C for customized inverse trip time
curve for step 1
tPRCrv1
0.005 - 3.000
-
0.001
0.500
Param PR for customized inverse reset
time curve for step 1
tTRCrv1
0.005 - 100.000
-
0.001
13.500
Param TR for customized inverse reset
time curve for step 1
tCRCrv1
0.1 - 10.0
-
0.1
1.0
Param CR for customized inverse reset
time curve for step 1
IN2>Min
1 - 2500
%IB
1
1
Minimum used operate residual current
level for step 2 in % of IBase, if IN2> is
less than IN2>Min then IN2> is set to
IN2>Min
IN2>Max
1 - 2500
%IB
1
2500
Maximum used operate residual current
level for step 2 in % of IBase, if IN2> is
greater than IN2>Max then IN2> is set to
IN2>Max
ResetTypeCrv2
Instantaneous
IEC Reset
ANSI reset
-
-
Instantaneous
Reset curve type for step2
(Instantaneous / IEC / ANSI)
tReset2
0.000 - 60.000
s
0.001
0.020
Reset time delay for step 2
tPCrv2
0.005 - 3.000
-
0.001
1.000
Param P for customized inverse trip time
curve for step 2
tACrv2
0.005 - 200.000
-
0.001
13.500
Param A for customized inverse trip time
curve for step 2
tBCrv2
0.00 - 20.00
-
0.01
0.00
Param B for customized inverse trip time
curve for step 2
tCCrv2
0.1 - 10.0
-
0.1
1.0
Param C for customized inverse trip time
curve for step 2
tPRCrv2
0.005 - 3.000
-
0.001
0.500
Param PR for customized inverse reset
time curve for step 2
tTRCrv2
0.005 - 100.000
-
0.001
13.500
Param TR for customized inverse reset
time curve for step 2
tCRCrv2
0.1 - 10.0
-
0.1
1.0
Param CR for customized inverse reset
time curve for step 2
IN3>Min
1 - 2500
%IB
1
1
Minimum used operate residual current
level for step 3 in % of IBase, if IN3> is
less than IN3>Min then IN3> is set to
IN3>Min
IN3>Max
1 - 2500
%IB
1
2500
Maximum used operate residual current
level for step 3 in % of IBase, if IN3> is
greater than IN3>Max then IN3> is set to
IN3>Max
ResetTypeCrv3
Instantaneous
IEC Reset
ANSI reset
-
-
Instantaneous
Reset curve type for step3
(Instantaneous / IEC / ANSI)
tReset3
0.000 - 60.000
s
0.001
0.020
Reset time delay for step 3
tPCrv3
0.005 - 3.000
-
0.001
1.000
Param P for customized inverse trip time
curve for step 3
Table continues on next page
1MRK 506 382-UEN A
Section 7
Current protection
Line distance protection REL650 2.2 IEC
189
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...