STARTCOMB
To make it possible to provide the directional information from a protection
function, a STARTCOMB block is used in between the application function and the
Start Matrix function.
The STARTCOMB function has one block input and 14 Boolean inputs that
convert the 14 Boolean inputs into a WORD output
STDIR
, see Figure
STDIRX=[b0, b1, b2, b3, b4, b5, b6, b7, b8, b9, b10, b11, b12, b13, b14]
b0=
START (start)
b1=
FW (forward)
b2=
REV (reverse)
b3=
STL1 (startL1)
b4=
FWL1 (forwardL1)
b5=
REVL1 (reverseL1)
b6=
STL2 (startL2)
b7=
FWL2 (forwardL2)
b8=
REVL2 (reverseL2)
b9=
STL3 (startL3)
b10=
FWL3 (forwardL3)
b11=
REVL3 (reverseL3)
b12=
STN (startN)
b13=
FWN (forwardN)
b14=
REVN (reverseN)
STARTCOMB
BLOCK
START
FW
REV
STL1
FWL1
REVL1
STL2
FWL2
REVL2
STL3
FWL3
REVL3
STN
FWN
REVN
STDI R
IEC16000166-2-en.vsdx
IEC16000166 V2 EN-US
Figure 249:
STARTCOMB
Protection functions
Some protection functions are provided with start and directional outputs, for
example:
Section 13
1MRK 506 382-UEN A
Logic
478
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...