The measured phase voltages and currents are provided as service values.
BLOCK
TRIP
ZACC
START_DLYD
I3P
U3P
AutoInitMode
Mode = Impedance
Mode = UILevel
Mode = UILvl&Imp
UILevel
Detector
IPh<
UPh<
BC
t
≥1
tSOTF
15ms
t
&
t
tDLD
≥1
DeadLine
SOTFUILevel
tOperate
t
tDuration
t
≥1
&
&
&
≥1
&
IEC07000084 V3 EN-US
Figure 59:
Simplified logic diagram for Automatic switch onto fault logic
6.3.8
Technical data
SEMOD173230-1 v1
M16043-1 v12
Table 49:
ZCVPSOF technical data
Parameter
Range or value
Accuracy
Operate voltage, detection of dead line
(1–100)% of
UBase
±0.5% of U
r
Operate current, detection of dead line
(1–100)% of
IBase
±1.0% of I
r
Time delay to operate for the switch onto fault
function
(0.03-120.00) s
±0.2% or ±20 ms
whichever is greater
Time delay for UI detection
(0.000-60.000) s
±0.2% or ±20 ms
whichever is greater
Delay time for activation of dead line detection
(0.000-60.000) s
±0.2% or ±20 ms
whichever is greater
Drop-off delay time of switch onto fault function
(0.000-60.000) s
±0.2% or ±30 ms
whichever is greater
Section 6
1MRK 506 382-UEN A
Impedance protection
134
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...