Name
Values (Range)
Unit
Step
Default
Description
RestoreFreq
45.00 - 65.00
Hz
0.01
49.90
Restore frequency value
tRestore
0.000 - 60.000
s
0.001
0.000
Restore time delay
tReset
0.000 - 60.000
s
0.001
0.000
Time delay for reset
Table 174:
SAPFRC Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base
Value groups
9.3.6
Operation principle
M14970-3 v9
Rate-of-change frequency protection SAPFRC is used to detect fast power system
frequency changes at an early stage. SAPFRC has a settable definite time delay. If
the rate-of-change of frequency remains below the set value, for negative rate-of-
change, for a time period equal to the chosen time delay, the TRIP signal is issued.
If the rate-of-change of frequency remains above the set value, for positive rate-of-
change, for a time period equal to the chosen time delay, the TRIP signal is issued.
To avoid an unwanted trip due to uncertain frequency measurement at low voltage
magnitude a voltage controlled blocking of the function is available, that is, if the
voltage is lower than the set blocking voltage
IntBlockLevel
the function is blocked
and no START or TRIP signal is issued. If the frequency recovers, after a
frequency decrease, a restore signal is issued.
9.3.6.1
Measurement principle
M14970-6 v8
The rate-of-change of the fundamental frequency of the selected voltage is
measured continuously, and compared with the set value,
StartFreqGrad
. Rate-of-
change frequency protection SAPFRC is also dependent on the voltage magnitude.
If the voltage magnitude decreases below the setting
IntBlockLevel
, SAPFRC is
blocked, and the output BLKDMAGN is issued. The sign of the setting
StartFreqGrad
, controls if SAPFRC reacts on a positive or on a negative change in
frequency. If SAPFRC is used for decreasing frequency that is, the setting
StartFreqGrad
has been given a negative value, and a trip signal has been issued,
then a 100 ms pulse is issued on the RESTORE output, when the frequency
recovers to a value higher than the setting
RestoreFreq
. A positive setting of
StartFreqGrad
, sets SAPFRC to START and TRIP for frequency increases.
To avoid oscillations of the output START signal, a hysteresis has been included.
9.3.6.2
Time delay
M14970-10 v7
Rate-of-change frequency protection SAPFRC has a settable definite time delay,
tDelay.
1MRK 506 382-UEN A
Section 9
Frequency protection
Line distance protection REL650 2.2 IEC
311
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...