the pulse length
•
the number of pulses, that is, the number of rising and falling flank pairs
In principle, more pulses may lead to reduced accuracy.
14.11.6.2
Memory storage
GUID-B49698FF-0AB2-4792-A7CB-5534313B6CA0 v2
The value of the accumulated time is retained in a non-volatile memory,
•
at every falling edge of the input
IN
•
at every even 6 minutes, after a rising edge of the input
IN
•
after a manual addition of time
Consequently in case of a power failure, there is a risk of losing the difference in
time between actual time and last time stored in the non-volatile memory.
14.11.7
Technical data
GUID-F5E124E3-0B85-41AC-9830-A2362FD289F2 v1
Table 452:
TEILGAPC Technical data
Function
Range or value
Accuracy
Time limit for alarm
supervision, tAlarm
(0 - 99999.9) hours
±0.1% of set value
Time limit for warning
supervision, tWarning
(0 - 99999.9) hours
±0.1% of set value
Time limit for overflow
supervision
Fixed to 99999.9 hours
±0.1%
1MRK 506 382-UEN A
Section 14
Monitoring
Line distance protection REL650 2.2 IEC
639
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...