PID-6836-OUTPUTSIGNALS v2
Table 353:
TEIGAPC Output signals
Name
Type
Description
WARNING
BOOLEAN
Indicator of the integrated time has reached the
warning limit
ALARM
BOOLEAN
Indicator of the integrated time has reached the
alarm limit
OVERFLOW
BOOLEAN
Indicator of the integrated time has reached the
overflow limit
ACCTIME
REAL
Integrated elapsed time in seconds
13.13.5
Settings
PID-6836-SETTINGS v2
Table 354:
TEIGAPC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
tWarning
1.00 - 999999.00
s
0.01
600.00
Time limit for warning supervision
tAlarm
1.00 - 999999.00
s
0.01
1200.00
Time limit for alarm supervision
13.13.6
Operation principle
GUID-04CC8365-DCDE-4DC7-BEF0-6EF8382305DD v3
The elapsed time integrator (TEIGAPC) provides
•
time integration, accumulating the elapsed time when a given binary signal has
been high
•
blocking and reset of the total integrated time
•
supervision of limit transgression and overflow, the overflow limit is fixed to
999999.9 seconds
•
retaining of the integrated value
Figure
describes the simplified logic of the function where the block “Time
Integration“ covers the logics for the first two items listed above while the block
“Transgression Supervision Plus Retain“ contains the logics for the last two.
1MRK 506 382-UEN A
Section 13
Logic
Line distance protection REL650 2.2 IEC
519
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...