Table 681:
IEC Inverse time characteristics for Voltage restrained time overcurrent protection
Function
Range or value
Accuracy
Operating characteristic:
(
)
1
=
×
-
æ
ö
ç
÷
ç
÷
è
ø
P
A
t
k
I
EQUATION1251-SMALL V1 EN-US
I = I
measured
/I
set
0.10 ≤ k ≤ 3.00
IEC 60255-151, ±5.0%
or ±40 ms whichever is
greater
IEC Normal Inverse
A=0.14, P=0.02
IEC Very inverse
A=13.5, P=1.0
IEC Inverse
A=0.14, P=0.02
IEC Extremely inverse
A=80.0, P=2.0
IEC Short time inverse
A=0.05, P=0.04
IEC Long time inverse
A=120, P=1.0
SEMOD116978-2 v10
Table 682:
Inverse time characteristics for overvoltage protection
Function
Range or value
Accuracy
Type A curve:
=
-
>
>
æ
ö
ç
÷
è
ø
t
k
U
U
U
EQUATION1436-SMALL V1 EN-US
U> = U
set
U = U
measured
k = (0.05-1.10) in
steps of 0.01
±5.0% or ±45 ms
whichever is greater
Type B curve:
2.0
480
0.035
32
0.5
n
n
k
t
U
U
U
IECEQUATION2423 V2 EN-US
k = (0.05-1.10) in
steps of 0.01
Type C curve:
3.0
480
0.035
32
0.5
n
k
t
U U
U
×
=
+
-
>
æ
ö
×
-
ç
÷
>
è
ø
IECEQUATION2421 V1 EN-US
k = (0.05-1.10) in
steps of 0.01
Programmable curve:
×
=
+
-
>
×
-
>
æ
ö
ç
÷
è
ø
P
k A
t
D
U
U
B
C
U
EQUATION1439-SMALL V1 EN-US
k = (0.05-1.10) in
steps of 0.01
A = (0.005-200.000)
in steps of 0.001
B = (0.50-100.00) in
steps of 0.01
C = (0.0-1.0) in steps
of 0.1
D = (0.000-60.000) in
steps of 0.001
P = (0.000-3.000) in
steps of 0.001
Section 23
1MRK 506 382-UEN A
Inverse time characteristics
902
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...