Function
Range or value
Accuracy
Independent time delay for gas
pressure alarm
(0.00 – 60.00) s
±0.2% or ±30 ms whichever is
greater
Independent time delay for gas
pressure lockout
(0.00 – 60.00) s
±0.2% or ±30 ms whichever is
greater
CB Contact Travel Time,
opening and closing
±3 ms
Remaining Life of CB
±2 operations
Accumulated Energy
±1.0% or ±0.5 whichever is
greater
14.5
Event function EVENT
SEMOD120002-1 v2
14.5.1
Identification
SEMOD167950-2 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Event function
EVENT
S00946 V1 EN-US
-
14.5.2
Functionality
M12805-6 v11
When using a Substation Automation system with LON or SPA communication,
time-tagged events can be sent at change or cyclically from the IED to the station
level. These events are created from any available signal in the IED that is
connected to the Event function (EVENT). The EVENT function block is used for
LON and SPA communication.
Analog, integer and double indication values are also transferred through the
EVENT function.
1MRK 506 382-UEN A
Section 14
Monitoring
Line distance protection REL650 2.2 IEC
585
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...