![ABB RELION 650 SERIES Technical Manual Download Page 107](http://html.mh-extra.com/html/abb/relion-650-series/relion-650-series_technical-manual_2122107.webp)
R
X
Z3
Z2
Z1
Z4
Z5
ZRV
R
X
Z
S
=0
Z
S
=Z1
Z
S
=2Z1
IEC15000056-1-en.vsdx
IEC15000056 V1 EN-US
Figure 35:
Mho, offset mho characteristics and the source impedance
influence on the mho characteristic
The mho characteristic has a dynamic expansion due to the source impedance.
Instead of crossing the origin, as for the mho to the left of figure
, which is only
valid where the source impedance (Zs) is zero, the crossing point is moved to the
coordinates of the negative source impedance given an expansion of the circle
shown to the right of figure
. Z1 denotes the complex positive sequence
impedance.
The magnitude of the polarizing voltage is determined completely by the positive
sequence voltage magnitude from before the fault. This will give a somewhat less
dynamic expansion of the mho circle during faults. However, if the source
impedance is high, the dynamic expansion of the mho circle might lower the
security of the function too much with high loading and mild power swing
conditions.
Basic operation characteristics
GUID-E6CC3CA7-72BE-40FC-A557-7BDB62F7BC1E v2
In ZMFPDIS, each zone measurement loop characteristic can be set to mho
characteristic or offset mho characteristic by setting
OpModePEZx
or
OpModePPZx
(where
x
is 1-5 depending on selected zone).
ZMFPDIS fixes zone 1 and 2 in
Forward
mode and zone RV in
Reverse
mode.
Zone 3-5 can be set to
Non-directional
,
Forward
or
Reverse
by setting the
parameter
DirModeZx
(where x is 3-5 depending on selected zone).
If
DirModeZx
(where
x
is 3-5 depending on selected zone) is selected as
Non-
directional
, the directional element will not have any effect on the measurement
loop and operation of the function. When
DirModeZx
(where
x
is 3-5 depending on
selected zone) is selected as
Forward
or
Reverse
, directional lines are introduced.
Information about the directional lines is given from the directional element. Basic
Mho and offset Mho characteristics with different mode settings are indicated in
figure
.
1MRK 506 382-UEN A
Section 6
Impedance protection
Line distance protection REL650 2.2 IEC
101
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...