execute command
position L1
t1>tExecutionFB, then
long-operation-time in
'cause' is set
open
close
close
open
position L3
close
open
position L2
t1
tExecutionFB timer
cmd termination L1
cmd termination L2
cmd termination L3
cmd termination
position
open
close
* The cmd termination will be delayed one execution sample .
*
APCtExecutionFB=IEC0
5000094=2=en=Original
.vsd
IEC05000094 V2 EN-US
Figure 200:
tExecutionFB
The parameter
tSynchrocheck
is used to define the maximum allowed time between
the execute command and the input SYNC_OK to become true. If SYNC_OK=true
at the time the execute command signal is received, the timer "tSynchrocheck" will
not start. The start signal for the synchronizing is obtained if the synchrocheck
conditions are not fulfilled.
The parameter
tSynchronizing
is used to define the maximum allowed time
between the start signal for synchronizing and the confirmation that synchronizing
is in progress.
1MRK 506 382-UEN A
Section 11
Control
Line distance protection REL650 2.2 IEC
401
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...