![ABB RELION 650 SERIES Technical Manual Download Page 550](http://html.mh-extra.com/html/abb/relion-650-series/relion-650-series_technical-manual_2122550.webp)
Name
Values (Range)
Unit
Step
Default
Description
I1DbRepInt
1 - 100000
Type
1
10
Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
I1ZeroDb
0 - 100000
m%
500
1000
Magnitude zero point clamping in
0,001% of range
I1Min
0.0 - 500.0
%IB
0.1
50.0
Minimum value in % of IBase
I1Max
0.0 - 500.0
%IB
0.1
200.0
Maximum value in % of IBase
I1RepTyp
Cyclic
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
-
-
Cyclic
Reporting type
I1AngDbRepInt
1 - 100000
s
1
10
Cyclic report interval (s)
I2DbRepInt
1 - 100000
Type
1
10
Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
I2ZeroDb
0 - 100000
m%
500
1000
Magnitude zero point clamping in
0,001% of range
I2Min
0.0 - 500.0
%IB
0.1
50.0
Minimum value in % of IBase
I2Max
0.0 - 500.0
%IB
0.1
200.0
Maximum value in % of IBase
I2RepTyp
Cyclic
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
-
-
Cyclic
Reporting type
I2LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range, common
for all limits
I2AngDbRepInt
1 - 100000
s
1
10
Cyclic report interval (s)
Table 385:
CMSQI Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
3I0HiHiLim
0.0 - 500.0
%IB
0.1
150.0
High High limit in % of IBase
3I0HiLim
0.0 - 500.0
%IB
0.1
120.0
High limit in % of IBase
3I0LowLim
0.0 - 500.0
%IB
0.1
80.0
Low limit in % of IBase
3I0LowLowLim
0.0 - 500.0
%IB
0.1
60.0
Low Low limit in % of IBase
I1HiHiLim
0.0 - 500.0
%IB
0.1
150.0
High High limit in % of IBase
I1HiLim
0.0 - 500.0
%IB
0.1
120.0
High limit in % of IBase
I1LowLim
0.0 - 500.0
%IB
0.1
80.0
Low limit in % of IBase
I1LowLowLim
0.0 - 500.0
%IB
0.1
60.0
Low Low limit in % of IBase
I1LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range, common
for all limits
I2HiHiLim
0.0 - 500.0
%IB
0.1
150.0
High High limit in % of IBase
I2HiLim
0.0 - 500.0
%IB
0.1
120.0
High limit in % of IBase
I2LowLim
0.0 - 500.0
%IB
0.1
80.0
Low limit in % of IBase
I2LowLowLim
0.0 - 500.0
%IB
0.1
60.0
Low Low limit in % of IBase
Section 14
1MRK 506 382-UEN A
Monitoring
544
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...