Figure 1. Shunt Trip. 

Catalog 

Voltage 

Peak Inrush 

Number 

Rating (1)

Current, A (2) 

Nominal RMS 

Current, mA 

SPST012 

12  Vdc 

3.0 

200 

SPST024 

24 Vac 

1.5 

140 

24 Vdc 

SPST048 

1.5 

110 

48 

48 

Vac 

Vdc 

SPST120 

1.5 

85 

125 

120 Vac 

Vdc 

SPST208 

208 Vac 

1.5 

50 

SPST240 

1.5 

40 

250 

240 Vac 

Vdc 

24-240 Vac devices are rated for 50/60 Hz.
Peak  inrush  current  is  present  for  2-6  ms  after  activation.

This  number  is  provided  so  that  fuses  and  supplies  can  be  chosen 

appropriately. 

Catalog 

Voltage 

Peak Inrush 

Number 

Rating (1) 

Current, A (2) 

Nominal RMS 
Current, mA 

SPSTL012 

12  Vdc 

19 

300 

SPSTL024 

15 

300 

24

24

 Vac 

 Vdc 

SPSTL048 

7.5 

200 

48 

48 

Vac 

Vdc 

SPSTL120 

3.0 

80 

120 

125 

Vac 

Vdc 

SPSTL208 

208 Vac 

1.9 

60 

SPSTL240 

1 .5 

45 

250

240 Vac 

 Vdc 

1

GEH

6284 

INSTRUCTIONS

Power Break® II Circuit Breaker Accessories 

Shunt Trip and Shunt Trip with Lockout

 

The  catalog  numbers  for  various  voltage  applications  are 
listed in Table 1 for the Shunt Trip and in Table 2 for the Shunt 
Trip with Lockout. 


Table 1. Catalog numbers and voltages for the Shunt Trip. 


Figure 2. Shunt Trip with Lockout. 

Introduction

The  Shunt  Trip  and  Shunt  Trip  with  Lockout  accessories, 

shown  in  Figures  1  and  2,  can  be  installed  in  800-4000 

ampere  frame  Power  Break®II  circuit  breakers.  These 

accessories allow the breaker to be tripped electrically from a 

remote location.

In  addition  to  providing  a  trip  signal  to  the  breaker,  the 
Shunt Trip accessories can be set up to interact with other 
Power Break II accessories, when used with a MicroVersaTrip 
PlusTM  or  MicroVersaTrip  PM™  Trip  Unit.  DIP  switches  on 
the rear of the breaker Trip Unit can configure the Shunt Trip 
accessories to activate a Bell Alarm-Alarm Only accessory or 
a  Bell  Alarm  with  Lockout  accessory  when  a  shunt  trip 
occurs.  The  Accessory  Configuration  section  below 
describes  how  this  can  be  done.  If  the  breaker  is  equipped 
with  a  Power+™  Trip  Unit,  it  is  configured  so  that  only 
protection trips will activate a Bell Alarm

­

Alarm Only or Bell 

Alarm with Lockout. 


Table 2 Catalog numbers and voltages for the Shunt Trip with Lockout.

Operation 

Apply control voltage to terminals 31 and 32 of the terminal 
strip  on  the  right  side  of  the  breaker  to  trip  the  circuit 
breaker. The Shunt Trip will cause the circuit breaker to trip 
when the control voltage is greater than 75% of the rated de 
voltage or 55% of the rated ac voltage. Control power to the 
Shunt  Trip  must  be  removed  before  the  breaker  can  be 
closed.  Control  power  to  the  Shunt  Trip  with  Lockout  must 
be removed for a minimum of 0.25 second before the breaker 
can be closed.  

(1)