Factory 

Switch 

Setting 

Function 

Disabled  Shunt trip activates Bell Alarm- Alarm Only 

Disabled 

UVR trip activates Bell Alarm-Alarm Only 

Enabled 

Protection trip activates Bell Alarm Alarm 

Only 

Disabled 

Shunt trip activates Bell Alarm with 

Lockout 

Disabled 

UVR trip activates Bell Alarm withLockout

Enabled 

Protection trip activates Bell Alarm with 
Lockout

When  a  Shunt  Trip  accessory  causes  the  breaker  to 
trip,  the  contacts  of  the  Bell  Alarm-Alarm  Only  also 
change state. (The  factory switch setting is disabled. )
When  an  Under  voltage Release  accessory causes  the 
breaker  to  trip,  the  contacts  of  the  Bell  Alarm-Alarm 
Only also change state. (The     factory switch setting is 
disabled.) 
When

 

a  protection  trip  (long-time,  short-time, 

instantaneous,  ground-fault,  or  protective-relay) 
occurs, the  contacts of  the  Bell  Alarm-Alarm Only  also 
change state. (The factory switch setting is enabled.) 
When  a  Shunt  Trip  accessory  causes  the  breaker  to 
trip,  the  contacts  of  the  Bell  Alarm  with  Lockout  also 
change state. (The factory switch setting is disabled.)
When  an  Under  voltage Release  accessory causes  the 
breaker  to  trip,  the  contacts  of  the  Bell  Alarm  with 
Lockout also change state. (The  factory switch setting 
is disabled. )
When

 

a  protection  trip  (long-time,  short-time, 

instantaneous,  ground-fault,  or  protective-relay) 
occurs, the contacts of the Bell Alarm with Lockout also 
change state. (The factory switch setting i s enabled.) 

Procedure for Changing Switch Settings 

Change  the  accessory  switch  settings  with  the  following 
procedure: 

WARNING:

  Before  beginning  this  procedure,  turn  the 

breaker  off,  disconnect  it  from  all  voltage  sources,  and 
discharge the closing springs. 

AVERTISSEMENT:

  Avant  de  commencer  cette  procédure, 

mettre  le  disjoncteur  en  position  OFF,  le  déconnecter  de 
toute  tension  d'alimentation,  et  désarmer  les  ressorts  de 
fermeture. 

2

3

4

5

Loosen  the  four  #10-32  screws  at  the  corner  of  the 
breaker cover.
Remove the cover from the breaker face.
Pull  the  Trip  Unit  locking  lever  to  the  right,  then  hold 
the Trip Unit near the battery cover and lift it straight 
out of the breaker.
Refer to Figure 5 and Table 3 to determine the switches 
to  be  changed.  Push  in  the  appropriate  "Enable"  or 
"Disable" side of the switch.
Confirm all switch settings before reinstalling the Trip 
Unit in the breaker.
Pull  the  Trip  Unit  locking  lever  to  the  right.  While 
holding  the  lever,  carefully  align  the  connector  on  the 
rear of the Trip Unit with the connector in the breaker. 
Press down on the Trip Unit, while holding it near the 
battery cover. When the Trip Unit  is fully seated, slide 
the locking lever back to the left.
Reinstall  the  breaker  top  cover  and  tighten  the  four 
#10-32 screws to 32 in-lb. 
Replace  the  trim  plate  and  tighten  the  four  #8-32 
screws to 20 in-lb. 
Verify that the switch settings are correct by inducing 
breaker  trips  from  the  Shunt  Trip  and  Undervoltage 
Release (if present) and checking the responses of the 
Bell  Alarm-Alarm  Only  and  Bell  Alarm  with  Lockout 
accessories.

ƈƓơƢƄƠƝƑƓƒƣƠƓ

Test the Shunt Trip for proper operation with the following 
procedure. 

Turn off the power to the Shunt Trip.
Close the breaker contacts.
Apply  at  least  55%  of  the  rated  ac  voltage  or  at 
least  75%  of  the  rated  de  voltage  to  the  Shunt 
Trip;  the breaker should trip immediately.

If a Bell Alarm-Alarm Only or Bell Alarm with Lockout is 
present, ensure that it activates (or does not activate) 
as  selected  by  the  MicroVersaTrip  Plus  or 
MicroVersaTrip PM Trip Unit. 

If  a  Shunt  Trip  with  Lockout  has  been  installed,  continue 

with the following steps: 

After the  breaker has  tripped and  with the  power  still 
applied  to  the  Shunt  Trip  with  Lockout,  attempt 
to close  the  breaker.  The  breaker  should  not  close 
nor attempt to close.
If a MicroVersaTrip Plus or MicroVersaTrip PM Trip Unit 
is  installed,  check  that  the  Trip  Unit  display  is 
active (powered). 
Remove power from the Shunt Trip with Lockout. 
Attempt  to  close  the  breaker;  it  should  close  as 
normal.

3


Table 3. Accessory switch settings, including factory defaults. 

Description of Switch Settings 

Following  are  descriptions  of  the  effects  of  each  accessory 

switch when it  is  enabled. 

1.

2.

3.

4.

5.

6.

5.

6.

7.
8.

1.
2.

.

4.

6

7

8

9

10

Loosen  the  four  #8-32  screws  on  the  breaker  trim-

plate assembly and remove the trim plate. 

1

.