(T) Multi-Function Input Terminal Parameters
420
• Turning ON the RT signal enables the second function, and turning ON the X9 signal enables the third function. The
following table shows the functions which can be changed to the second or third function.
NOTE
• RT signal is assigned to the terminal RT in the initial status. Set "3" in any of
Pr.178 to Pr.189 (Input terminal function
selection)
to assign the RT signal to another terminal.
• When both the RT signal and X9 signal are ON, the X9 signal (third function) is prioritized.
• Changing the terminal assignment using
Pr.178 to Pr.189 (Input terminal function selection)
may affect the other functions.
Set parameters after confirming the function of each terminal.
???????
Parameters referred to
Pr.178 to Pr.189 (Input terminal function selection)
Function
First function
Parameter number
Second function
Parameter number
Third function
Parameter number
Refer to
page
Torque boost
Pr.0
Pr.46
Pr.112
Base frequency
Pr.3
Pr.47
Pr.113
Acceleration time
Pr.7
Pr.44
Pr.110
Deceleration time
Pr.8
Pr.44, Pr.45
Pr.110, Pr.111
Electronic thermal O/L
relay
Pr.9
Pr.51
Free thermal
Pr.600 to Pr.604
Pr.692 to Pr.696
Motor permissible load
level
Pr.607
Pr.608
Stall prevention
Pr.22
Pr.48, Pr.49
Pr.114, Pr.115
Pr.71
Pr.450
Pr.80 to Pr.84, Pr.90 to Pr.94,
Pr.298, Pr.702, Pr.706,
Pr.707, Pr.711, Pr.712,
Pr.717, Pr.721, Pr.724,
Pr.725, Pr.859
Pr.453 to Pr.457, Pr.560,
Pr.458 to Pr.462, Pr.738 to Pr.747,
Pr.860
Excitation current low-
speed scaling factor
Pr.85, Pr.86
Pr.565, Pr.566
Speed control gain
(Advanced magnetic
flux vector)
Pr.89
Pr.569
Offline auto tuning
Pr.96
Pr.463
Online auto tuning
Pr.95
Pr.574
PID control
Pr.127 to Pr.134
Pr.753 to Pr.758
PID Pre-charge
function
Pr.760 to Pr.764
Pr.765 to Pr.769
Brake sequence
Pr.278 to Pr.285, Pr.639,
Pr.640
Pr.641 to Pr.648, Pr.650, Pr.651
Droop control
Pr.286 to Pr.288, Pr.994,
Pr.995
Pr.679 to Pr.683
Motor control method
Pr.800
Pr.451
Speed control gain
Pr.820, Pr.821
Pr.830, Pr.831
Analog input filter
Pr.822, Pr.826
Pr.832, Pr.836
Speed detection filter
Pr.823
Pr.833
Torque control gain
Pr.824, Pr.825
Pr.834, Pr.835
Torque detection filter
Pr.827
Pr.837
The function can be changed by switching the RT signal ON/OFF while the inverter is stopped. If a signal is switched during operation, the
operation method changes after the inverter stops. (
Pr.450
9999)
When the RT signal is OFF, the first function is selected and when it is ON, the second function is selected.