Causes and corrective actions
646
Abbreviation
E.MP
FR-LU08
—
Name
Magnetic pole position unknown
Description
When the offset value between the PM motor home magnetic pole position and the home position of the
encoder (position detector) is unknown, the protective circuit is activated to stop the inverter output.
Check point
• Check that the encoder position tuning was performed.
• Check that the encoder position tuning ended properly. When
Pr.1105 Encoder magnetic pole position
offset
= "9999", the encoder position tuning does not end properly.
Corrective action
• Perform encoder position tuning with
Pr.373 Resolver position tuning setting/status
. (Refer to the
Instruction Manual of the encoder option.)
• Remove the cause of the tuning error, and perform tuning again. (Refer to the Instruction Manual of the
encoder option.)
Abbreviation
E.EF
FR-LU08
Fault
Name
External fault during output operation
Description
When the X32 signal turns OFF (the contact opens) due to an external fault or other factor, the inverter output
is shut off. This function is available when "32" is set in any of
Pr.178 to Pr.189 (Input terminal function
selection)
. This protective function is not available in the initial status (X32 signal is not assigned).
Check point
• Check that the X32 signal is OFF.
Corrective action
• Make sure that there is no problem in starting operation, and turn ON the X32 signal.
Abbreviation
E.LCI
FR-LU08
Lost mA Input
FR-PU07
Fault
Name
4 mA input fault
Description
The inverter trips when the analog input current is 2 mA or less for the time set in
Pr.778 4 mA input check
filter
. This function is available when
Pr.573 4 mA input check selection
= "2 or 3". (Refer to
This function is not available in the initial status.
Check point
• Check for a break in the wiring for the analog current input.
• Check that the
Pr.778
setting is not too short.
Corrective action
• Check the wiring for the analog current input.
• Set the
Pr.778
setting larger.
Abbreviation
E.PCH
FR-LU08
Precharge Error
FR-PU07
Fault
Name
Pre-charge fault
Description
• The inverter trips when the pre-charge time exceeds
Pr.764 Pre-charge time limit
.
• The inverter trips when the measured value exceeds
Pr.763 Pre-charge upper detection level
during pre-
charging.
• This function is available when
Pr.764 and Pr.763
are set. This protective function is not available in the
initial status.
Check point
• Check that the
Pr.764
setting is not too short.
• Check that the
Pr.763
setting is not too small.
• Check that the
Pr.127 PID control automatic switchover frequency
setting is not too low.
• Check for a break in the connection to the pump.
Corrective action
• Set the
Pr.764
setting longer.
• Set the
Pr.763
setting larger.
• Set the
Pr.127
setting higher.
• Check the connection to the pump.
Abbreviation
E.PID
FR-LU08
FR-PU07
PID Signal Error
Name
PID signal fault
Description
The inverter trips if the measured value exceeds the PID upper limit or PID lower limit parameter setting, or
the absolute deviation value exceeds the PID deviation parameter setting during PID control.
Set this function in
Pr.131 PID upper limit, Pr.132 PID lower limit, Pr.553 PID deviation limit, and Pr.554
PID signal operation selection
. (Refer to
.) This protective function is not available in the initial
status.
Check point
• Check the meter for a failure or break.
• Check that the parameter settings are correct.
Corrective action
• Check that the meter has no failure or break.
• Set the parameters correctly.