505
5
GROUP
A
NOTE
• During the pre-charge operation, it is regarded as integrated value=estimated value. The motor speed may drop shortly from
the automatic switchover frequency depending on the parameter settings.
• Parameter changes and switchover to the second PID control are applied immediately. If PID control has not started when
the settings were changed, PID control starts with changed settings. (If PID control has already started, these settings do not
apply. If the changed settings already satisfies a condition to start PID control, the PID control starts as soon as these are
changed.)
• The pre-charge also ends when PID control is set to invalid, the start command has been turned OFF, and output has been
shut off.
Example of pre-charge operation
• When the measured amount reaches the pre-charge ending level (
Pr.761 Pre-charge ending level
"9999")
The pre-charge operation ends when the measured value reaches the
Pr.761
setting or higher, then the PID control is
performed.
• When the elapsed time reaches the pre-charge ending time (
Pr.762 Pre-charge ending time
"9999")
The pre-charge operation ends when the pre-charge time reaches the
Pr.762
setting or higher, then the PID control is
performed.
• When the signal is input to end the pre-charge operation
When the X77 signal turns ON, the pre-charge operation ends, and the PID control starts. (If a start command is given while
the X77 signal is ON, the pre-charge operation is not performed, and PID control starts.)
Pr.127
0Hz
STF
PID control
Pr.761
Measured value[PSI]
Output frequency[Hz]
Y49
Ending level
Time
Time
Pr.127
0Hz
STF
PID control
Pr.762
Output frequency[Hz]
Y49
Ending time
Time
X77
Pr.127
0Hz
STF
PID control
Output frequency[Hz]
Y49
Time
10ms or more