• The second PID function parameters and signals function in the same way as the following parameters and signals of the
first PID function. Refer to the first PID function when setting the second PID functions.
NOTE
• Even if the X14 signal is ON, PID control is stopped and multi-speed or JOG operation is performed when the RH, RM, RL, or
REX signal (multi-speed operation) or JOG signal (JOG operation) is input.
• PID control is invalid under the following settings.
Pr.79 Operation mode selection
= "6" (Switchover mode)
• Note that input to the terminal 1 is added to the terminals 2 and 4 inputs. For example when
Pr.128
= "20 or 21", the terminal
1 input is considered as a set point and added to the set point of the terminal 2.
• To use terminal 4 and 1 inputs in PID control, set "0" (initial value) to
Pr.858 Terminal 4 function assignment
and
Pr.868
Terminal 1 function assignment
. When a value other than "0", PID control is invalid.
• Changing the terminal assignment using
Pr.178 to Pr.189 or Pr.190 to Pr.196
may affect other functions. Set parameters
after confirming the function of each terminal.
• When PID control is selected, the minimum frequency becomes the frequency of
Pr.902
and the maximum frequency
becomes the frequency of
Pr.903
.
(The
Pr.1 Maximum frequency
and
Pr.2 Minimum frequency
settings also are valid.)
• During PID operation, the remote operation function is invalid.
• When control is switched to PID control during normal operation, the frequency during that operation is not carried over, and
the value resulting from PID calculation referenced to 0 Hz becomes the command frequency.
Classification
First PID function parameters
Second PID function parameters
Pr.
Name
Pr.
Name
Parameter
127
PID control automatic switchover
frequency
754
Second PID control automatic switchover
frequency
128
PID action selection
753
Second PID action selection
129
PID proportional band
756
Second PID proportional band
130
PID integral time
757
Second PID integral time
131
PID upper limit
1143
Second PID upper limit
132
PID lower limit
1144
Second PID lower limit
133
PID action set point
755
Second PID action set point
134
PID differential time
758
Second PID differential time
553
PID deviation limit
1145
Second PID deviation limit
554
PID signal operation selection
1146
Second PID signal operation selection
575
Output interruption detection time
1147
Second output interruption detection time
576
Output interruption detection level
1148
Second output interruption detection level
577
Output interruption cancel level
1149
Second output interruption cancel level
609
PID set point/deviation input selection
1140
Second PID set point/deviation input
selection
610
PID measured value input selection
1141
Second PID measured value input selection
Classification
First PID function parameters
Second PID function parameters
signal
Name
signal
Name
Input signal
X14
PID control valid terminal
X80
Second PID control valid terminal
X64
PID forward/reverse action switchover
X79
Second PID forward/reverse action
switchover
X72
PID P control switchover
X73
Second PID P control switchover
Output signal
FUP
PID upper limit
FUP2
Second PID upper limit
FDN
PID lower limit
FDN2
Second PID lower limit
RL
PID forward/reverse rotation output
RL2
Second PID forward/reverse rotation output
PID
During PID control activated
PID2
Second During PID control activated
SLEEP
PID output interruption
SLEEP2
During second PID output shutoff
Y48
PID deviation limit
Y205
Second PID deviation limit
PID action
Frequency
command
PID set point
Frequency command
during normal operation
ON
Operation when control is switched to PID control during normal operation
Normal operation
PID operation