Relationship between the analog input terminal function and the
calibration parameter
• Calibration parameter according to the terminal 1 function
• Calibration parameter according to the terminal 4 function
Torque change at maximum analog input (Pr.920, Pr.933)
• To only change the torque setting (gain) of the maximum analog input voltage (current), set to
Pr.920, Pr.933
.
Pr.868
setting
Terminal function
Calibration parameter
Bias setting
Gain setting
0
(initial
value)
Frequency (speed)
setting auxiliary
Pr.902 Terminal 2 frequency setting bias
frequency
Pr.902 Terminal 2 frequency setting bias
Pr.904 Terminal 4 frequency setting bias
frequency
Pr.904 Terminal 4 frequency setting bias
Pr.125 (Pr.903) Terminal 2 frequency
setting gain frequency
Pr.903 Terminal 2 frequency setting gain
Pr.126 (Pr.905) Terminal 4 frequency
setting gain frequency
Pr.905 Terminal 4 frequency setting gain
1
Magnetic flux
command
Pr.919 Terminal 1 bias command (torque)
Pr.919 Terminal 1 bias (torque)
Pr.920 Terminal 1 gain command (torque)
Pr.920 Terminal 1 gain (torque)
2
Regenerative driving
torque limit
Pr.919 Terminal 1 bias command (torque)
Pr.919 Terminal 1 bias (torque)
Pr.920 Terminal 1 gain command (torque)
Pr.920 Terminal 1 gain (torque)
3
Torque command
4
Stall prevention
operation level
/torque limit/torque
command
5
Forward/reverse
rotation speed limit
Pr.917 Terminal 1 bias frequency (speed)
Pr.917 Terminal 1 bias (speed)
Pr.918 Terminal 1 gain frequency (speed)
Pr.918 Terminal 1 gain (speed)
6
Torque bias input
Pr.919 Terminal 1 bias command (torque)
Pr.919 Terminal 1 bias (torque)
Pr.920 Terminal 1 gain command (torque)
Pr.920 Terminal 1 gain (torque)
9999
No function
―
―
Adjustment of the bias and gain for stall prevention operation level is done by
Pr.148 Stall prevention level at 0 V input and Pr.149 Stall
prevention level at 10 V input
.
Pr.858
setting
Terminal function
Calibration parameter
Bias setting
Gain setting
0
(initial
value)
Frequency (speed)
command/
Speed limit
Pr.904 Terminal 4 frequency setting bias
frequency
Pr.904 Terminal 4 frequency setting bias
Pr.126 (Pr.905) Terminal 4 frequency
setting gain frequency
Pr.905 Terminal 4 frequency setting gain
1
Magnetic flux
command
Pr.932 Terminal 4 bias command (torque)
Pr.932 Terminal 4 bias (torque)
Pr.933 Terminal 4 gain command (torque)
Pr.933 Terminal 4 gain (torque)
4
Stall prevention
operation level
/torque limit
Pr.932 Terminal 4 bias command (torque)
Pr.932 Terminal 4 bias (torque)
Pr.933 Terminal 4 gain command (torque)
Pr.933 Terminal 4 gain (torque)
9999
No function
―
―
Adjustment of the bias and gain for stall prevention operation level is done by
Pr.148 Stall prevention level at 0 V input and Pr.149 Stall
prevention level at 10 V input
.