(E) Environment setting parameters
256
Automatic parameter setting (Pr.999)
• Select which parameters to automatically set from the table below, and set them in
Pr.999
. Multiple parameter settings are
changed automatically. Refer to
for the list of parameters that are changed automatically.
NOTE
• If the automatic setting is performed with
Pr.999
or the automatic parameter setting mode, the settings including the changed
parameter settings (changed from the initial setting) will be automatically changed. Before performing the automatic setting,
confirm that changing the parameters will not cause any problem.
PID monitor indicator setting (Pr.999 = "1 or 2")
Enabled when the FR-PU07-01 is used.
Pr.999
Setting
Description
1
Sets the standard monitor indicator setting of PID control.
2
Automatically sets the monitor indicator for PID control.
10
Automatically sets the communication parameters for the GOT connection with a PU
connector ("Controller Type" in GOT: FREQROL 500/700/800, SENSORLESS SERVO)
11
Automatically sets the communication parameters for the GOT connection with RS-485
terminals ("Controller Type" in GOT: FREQROL 500/700/800, SENSORLESS SERVO)
12
Automatically sets the communication parameters for the GOT connection with a PU
connector ("Controller Type" in GOT: FREQROL 800 (Automatic Negotiation))
13
Automatically sets the communication parameters for the GOT connection with RS-485
terminals ("Controller Type" in GOT: FREQROL 800 (Automatic Negotiation))
20
50 Hz rated frequency
Sets the related parameters of the rated frequency according to
the power supply frequency
21
60 Hz rated frequency
Pr.
Name
Initial value
Pr.999="1"
Pr.999="2"
Refer to page
759
PID unit selection
9999
9999
4
1142
Second PID unit selection
9999
9999
4
774
Operation panel monitor selection 1
9999
9999
52
775
Operation panel monitor selection 2
9999
9999
53
776
Operation panel monitor selection 3
9999
9999
54
934
PID display bias coefficient
9999
9999
0
935
PID display gain coefficient
9999
9999
100
1136
Second PID display bias coefficient
9999
9999
0
1138
Second PID display gain coefficient
9999
9999
100
—
3-step monitor setting
—
Disabled
—
—
Direct setting
—
Disabled
—
—
Dedicated parameter list function
—
Disabled
—