(A) Application parameters
456
• To enable the self power management function for the separated converter type, enable the self power management
function also on the converter unit side. To activate the self power management function when a converter unit fault occurs,
connect the terminal to which Y17 signal of the converter unit is assigned and the terminal to which X94 signal of the
inverter is assigned.
• To use the X94 signal, set "94" in any of
Pr.178 to Pr.189 (Input terminal function selection)
to assign the function to an
input terminal.
NOTE
• When the start signal is turned OFF before the time set in
Pr.137
has passed after the start signal is turned ON, the inverter
does not start and the MC1 signal is turned OFF after the time set in
Pr.254
has passed.
If the start signal is turned ON again before the time set in
Pr.254
has passed, the inverter immediately starts outputting.
• At inverter reset, the status of the MC1 signal is held and operation of the magnetic contactor is not performed.
• When the inverter stops the output due to, for example, the Output stop (MRS) signal, the MC1 signal is turned OFF after the
time set in
Pr.254
has passed.
• During the stop, turning ON the External DC injection brake operation start signal (X13) and Pre-excitation/servo ON signal
(LX) turns ON the MC1 signal.
• To avoid inverter reset when starting to supply power to the main circuit when power is already supplied only to the control
circuit, set 100 or more in
Pr.30
. (For the separated converter type, setting
Pr.30
of the converter unit is also required.)
• When supplying power to the main circuit is started when power is supplied only to the control circuit, there is a little waiting
time before starting.
• Repeated operation of the magnetic contactor due to frequent start and stop or activation of the protective function may
shorten the inverter life.
• Changing the terminal assignment using
Pr.178 to Pr.189 (Input terminal function selection) and Pr.190 to Pr.196
(Output terminal function selection)
may affect the other functions. Set parameters after confirming the function of each
terminal.
???????
Parameters referred to
Pr.11 DC injection brake operation time
Pr.30 Regenerative function selection
Pr.190 to Pr.196 (Output terminal function selection)
Y17 output signal
(on the converter unit side)
MC1 output signal
(inverter side)
MC1 output signal
actual operation
Main circuit power
supply
OFF
OFF
OFF
Stop
OFF
ON
OFF
Stop
ON
OFF
OFF
Stop
ON
ON
ON
Supplied
STF
MC1
ON
Time
Pr.254
Output frequency
(Hz)
ON
OFF
Pr.137
Pr.254
Pr.137
STF
MC1
ON
Time
Output frequency
(Hz)
ON
ON
OFF
OFF