(H) Protective function parameter
338
To further prevent a trip (Pr.154)
• When
Pr.154
Voltage reduction selection during stall prevention operation
= "0, 10", the output voltage is reduced. By
making this setting, an overcurrent trip becomes less likely to occur. Use this setting when torque reduction does not pose
a problem. (Under V/F control, the output voltage is reduced only during the stall prevention operation is activated.)
• Set
Pr.154
= "10, 11" when the overvoltage protective function (E.OV[ ]) activates during stall prevention operation in an
application with large load inertia. Note that turning OFF the start signal (STF/STR) or varying the frequency command
during stall prevention operation may delay the acceleration/deceleration start.
???????
Parameters referred to
Pr.22 torque limit level
Pr.73 Analog input selection
Pr.178 to Pr.189 (Input terminal function selection)
Pr.190 to Pr.196 (Output terminal function selection)
Pr.858 Terminal 4 function assignment, Pr.868 Terminal 1 function assignment
Pr.154
E.OC[ ] countermeasure
E.OV[ ] countermeasure
0
Effective
―
1 (initial value)
―
―
10
Effective
Effective
11
―
Effective
CAUTION
Do not set the stall prevention operation current too low.
Doing so will reduce the generated torque.
Be sure to perform a test run.
Stall prevention operation during acceleration may extend the acceleration time.
Stall prevention operation during constant-speed operation may cause sudden speed changes.
Stall prevention operation during deceleration may extend the deceleration time.