Measurement of main circuit voltages, currents and powers
PRECAUTIONS FOR MAINTENANCE AND INSPECTION
667
7
Measuring points and instruments
Use an FFT to measure the output voltage accurately. A tester or general measuring instrument cannot measure accurately.
When the setting of
Pr.195 ABC1 terminal function selection
is the positive logic
Item
Measuring point
Measuring instrument
Remarks (reference measured value)
Power supply voltage
V1
Across R/L1 and S/L2,
S/L2 and T/L3,
T/L3 and R/L1
Digital power meter (for inverter)
Commercial power supply
Within permissible AC voltage fluctuation
(Refer to
Power supply side
current
I1
R/L1, S/L2, T/L3 line
current
Power supply side
power
P1
R/L1, S/L2, T/L3 and
Across R/L1 and S/L2,
S/L2 and T/L3,
T/L3 and R/L1
P1 = W11 + W12 + W13 (3-wattmeter method)
Power supply side
power factor
Pf1
Calculate after measuring power supply voltage, power supply side current and power supply side power.
Output side voltage
V2
Across U and V, V
and W, and W and U
Digital power meter (for inverter)
Difference between the phases is within 1% of the
maximum output voltage.
Output side current
I2
U, V and W line
currents
Difference between the phases is 10% or lower of the
inverter rated current.
Output side power
P2
U, V, W and
across U and V, V
and W
Digital power meter (for inverter)
P2 = W21 + W22
2-wattmeter method (or 3-wattmeter method)
Output side power
factor
Pf2
Calculate in similar manner to power supply side power factor.
Converter output
Across P/+ and N/-
Tester such as a digital multimeter
Inverter LED is lit. 1.35
V1
Frequency setting
signal
Across 2, 4(+) and 5
Tester such as a digital
multimeter, or moving-coil type
instrument
(internal resistance 50 k
Ω
or more)
0 to 10 VDC, 4 to 20 mA
"5" is
common
Across 1(+) and 5
0 to ±5 VDC and 0 to ±10 VDC
Frequency setting
power supply
Across 10(+) and 5
5.2 VDC
Across 10E(+) and 5
10 VDC
Frequency meter
signal
Start signal
Select signal
Reset signal
Output stop signal
Across AM(+) and 5
Approximately 10 VDC at maximum
frequency
(without frequency meter)
Across FM(+) and
SD
Approximately 5 VDC at maximum
frequency
(without frequency meter)
Pulse width T1: Adjust with
Pr.900
.
Pulse cycle T2: Set with
Pr.55
.
(frequency monitor only)
"SD" is
common
Across STF, STR,
RH, RM, RL, JOG,
RT, AU, STP (STOP),
CS, RES, MRS(+)
and SD (for sink
logic)
When open
20 to 30 VDC
ON voltage: 1 V or less
Fault signal
Across A1 and C1
Across B1 and C1
Tester such as a digital multimeter
[Normal]
[Fault]
Across A1 and C1 Discontinuity
Continuity
Across B1 and C1 Continuity
Discontinuity
Pf
1
P
1
3V
1
I
1
------------------------ 100
=
%
Pf
2
P
2
3V
2
I
2
------------------------ 100
=
%
8VDC
T1
T2