Connection of motor with encoder (vector control)
61
2
Switches of the FR-A8AP
• Encoder type selection switch (SW3)
Selects either the differential line driver or complementary setting.
It is initially set to the differential line driver. Switch its position according to the
output circuit.
• Terminating resistor selection switch (SW1)
Selects ON/OFF of the internal terminating resistor.
Set the switch to ON (initial status) when an encoder output type is differential
line driver, and set to OFF when complementary.
ON: with internal terminating resistor (initial status)
OFF:
without internal terminating resistor
NOTE
• Set all switches to the same setting (ON/OFF).
• Set the switch "OFF" when sharing an encoder with another unit (NC
(computerized numerical controller), etc.) having a terminating resistor
under the differential line driver setting.
• The SW2 switch is for manufacturer setting. Do not change the setting.
Encoder specification
NOTE
• Encoder with resolution of 1000 to 4096 pulse/rev is recommended.
Item
Specification
Resolution
0 to 4096 Pulse/Rev (setting by
Pr. 369
)
Power supply voltage
5 V, 12 V, 15 V, 24 V
Output signal form
A, B phases (90° phase shift)
Z phase: 1 pulse/rev
Output circuit
Differential line driver or complementary
Complementary
Differential line
driver (initial status)
1
2
3
4
O
N
1
2
O
N
SW2
SW3
SW1
Internal terminating
resistor-ON
(initial status)
Internal terminating
resistor-OFF
1
2
3
4
O
N
1
2
O
N
SW2
SW3
SW1