Parameter List
Parameter list (by parameter number)
115
Pr.
List
5
Regenera
ti
on avoidanc
e
fu
ncti
on
882
G120
Regeneration avoidance operation
selection
0 to 2
1
0
883
G121
Regeneration avoidance operation
level
300 to 1200 V
0.1V
940 V DC
884
G122
Regeneration avoidance at
deceleration detection sensitivity
0 to 5
1
0
885
G123
Regeneration avoidance
compensation frequency limit value
0 to 590 Hz, 9999
0.01 Hz
6 Hz
886
G124
Regeneration avoidance voltage
gain
0 to 200%
0.1%
100%
Free
paramet
ers
888
E420
Free parameter 1
0 to 9999
1
9999
889
E421
Free parameter 2
0 to 9999
1
9999
Energy sa
ving moni
tor
891
M023
Cumulative power monitor digit
shifted times
0 to 4, 9999
1
9999
892
M200
Load factor
30 to 150%
0.1%
100%
893
M201
Energy saving monitor reference
(motor capacity)
0.1 to 55 kW
0.01 kW
Rated inverter
capacity
0 to 3600 kW
0.1 kW
894
M202
Control selection during
commercial power-supply
operation
0 to 3
1
0
895
M203
Power saving rate reference value
0, 1, 9999
1
9999
896
M204
Power unit cost
0 to 500, 9999
0.01
9999
897
M205
Power saving monitor average time
0 to 1000 h, 9999
1 h
9999
898
M206
Power saving cumulative monitor
clear
0, 1, 10, 9999
1
9999
899
M207
Operation time rate (estimated
value)
0 to 100%, 9999
0.1%
9999
Calib
ratio
n
parameters
900
M310
FM terminal calibration
-
-
-
901
M320
AM terminal calibration
-
-
-
902
T200
Terminal 2 frequency setting bias
frequency
0 to 590 Hz
0.01 Hz
0 Hz
902
T201
Terminal 2 frequency setting bias
0 to 300%
0.1%
0%
903
(125)
T202
Terminal 2 frequency setting gain
frequency
0 to 590 Hz
0.01 Hz
60 Hz
903
T203
Terminal 2 frequency setting gain
0 to 300%
0.1%
100%
904
T400
Terminal 4 frequency setting bias
frequency
0 to 590 Hz
0.01 Hz
0 Hz
904
T401
Terminal 4 frequency setting bias
0 to 300%
0.1%
20%
905
(126)
T402
Terminal 4 frequency setting gain
frequency
0 to 590 Hz
0.01 Hz
60 Hz
905
T403
Terminal 4 frequency setting gain
0 to 300%
0.1%
100%
917
T100
Terminal 1 bias frequency (speed)
0 to 590 Hz
0.01 Hz
0 Hz
917
T101
Terminal 1 bias (speed)
0 to 300%
0.1%
0%
918
T102
Terminal 1 gain frequency (speed)
0 to 590 Hz
0.01 Hz
60 Hz
918
T103
Terminal 1 gain (speed)
0 to 300%
0.1%
100%
Functio
n
Pr.
Pr.
group
Name
Setting range
Minimum
setting
increments
Initial value
Refer
to
page
Customer
settin
g