(E) Environment setting parameters
250
Initial values differ depending on the rating as follows.
The rated current and motor capacity differ depending on the inverter capacity. Refer to the inverter rated specifications
)
.
The initial value for the FR-A860-00027 is set to the 85% of the inverter rated current.
• Setting
Pr.292 Automatic acceleration/deceleration
= "5 or 6 (lift mode)" will change the stall prevention operation level
as shown below.
NOTE
• When
Pr.570
="0" (SLD rating), carrier frequency automatic reduction is enabled regardless of the setting in
Pr.260 PWM
frequency automatic switchover
.
• To use the FR-A860-01080 in the LD and SLD ratings, a DC reactor corresponding to the applied motor is required.
• Setting the LD or SLD rating to the FR-A860-01080 changes their parameter setting increments and setting ranges in the
same way as for the FR-A860-01440 or higher. For example, the setting increment and the setting range of
Pr.9
will change
from "0.01 A" to "0.1 A" and from "0 to 500 A" to "0 to 3600 A". For the setting of each parameter, refer to the parameter list
(on
???????
Parameters referred to
Pr.260 PWM frequency automatic switchover
150
Output current detection level
110%
120%
150%
200%
165
Stall prevention operation level for restart
110%
120%
150%
200%
557
Current average value monitor signal
output reference current
SLD rated
current
LD rated
current
ND rated
current
HD rated
current
874
OLT level setting
110%
120%
150%
200%
893
Energy saving monitor reference (motor
capacity)
SLD rated motor
capacity
LD rated motor
capacity
ND rated motor
capacity
HD rated motor
capacity
Pr.
Pr.570
setting
FR-A860-[]
00027
00061
00090
00170
00320
00450
00680
01080
01440
01670 or
higher
0
(%)
0, 1
3
2
2
1
1
1
1
1
1
1
2
5
3
2
2
1
1
1
1
1
1
3
5
3
3
2
1
1
1
1
1
1
7
(s)
0, 1
5
5
5
15
15
15
15
15
15
15
2, 3
5
5
5
5
15
15
15
15
15
15
8
(s)
0, 1
10
10
10
30
30
30
30
30
30
30
2, 3
5
5
5
5
15
15
15
15
15
15
Pr.
Setting
Pr.570 setting
Refer to
page
0
1
2 (Initial value)
3
292
5
110%
120%
150%
200%
6
115%
140%
180%
230%
Pr.
Name
Pr.570 setting
Refer
to page
0
1
2
(Initial value)
3