(M) Monitor display and monitor output signal
384
5.11.9
Output torque detection
NOTE
• Changing the terminal assignment using
Pr.190 to Pr.196 (Output terminal function selection)
may affect the other
functions. Set parameters after confirming the function of each terminal.
???????
Parameters referred to
Pr.190 to Pr.196 (Output terminal function selection)
A signal is output when the motor torque is higher than the setting.
This function can be used for electromagnetic brake operation, open signal, etc.
Pr.
Name
Initial value
Setting range
Description
864
M470
Torque detection
150%
0 to 400%
Set the torque value where the TU
signal turns ON.
• The Torque detection (TU) signal turns ON when the
output torque reaches the detection torque value set in
Pr.864
or higher. The TU signal turns OFF when the
output torque drops lower than the detection torque
value.
•
Pr.864
is not available under V/F control.
• For the TU signal, set "35 (positive logic) or 135 (negative
logic)" in one of
Pr.190 to Pr.196 (Output terminal
function selection)
to assign the function to the output
terminal.
Magnetic flux
Magnetic flux
Magnetic flux
Sensorless
Sensorless
Sensorless
Vector
Vector
Vector
PM
PM
PM
Time
ON
TU
OFF
Output torque (%)
Pr.864