(T) Multi-Function Input Terminal Parameters
422
3-wire type (STF, STR, STP (STOP) signal)
• The following figure shows the connection in 3-wire type.
• Start self-holding function is enabled when the STP (STOP) signal is turned ON. In such case, forward/reverse signal will
only operate as start signal.
• Even if start signal (STF or STR) is turned ON and then OFF, the start signal will be maintained and it will start. To change
the rotation direction, turn STR (STF) ON once and then OFF.
• The inverter will perform deceleration stop by turning the STP (STOP) signal OFF once.
NOTE
• The STP (STOP) signal is assigned to the terminal STP (STOP) by the initial setting. Set "25" in any of
Pr.178 to Pr.189
to
assign the STP (STOP) signal to another terminal.
• When the JOG operation is enabled by turning ON the JOG signal, STOP signal will be disabled.
• Even when the output is stopped by turning ON the MRS signal, self-holding function is not canceled.
Start signal selection
???????
Parameters referred to
Pr.4 to Pr.6 (Multi-speed setting)
Pr.178 to Pr.189 (Input terminal function selection)
3-wire type connection example (Pr.250 = "9999")
3-wire type connection example (Pr.250 = "8888")
STF
STR
Pr.250 setting and inverter condition
0 to 100 s, 9999
1000 s to 1100 s, 8888
OFF
OFF
Stop
Stop
OFF
ON
Reverse rotation
ON
OFF
Forward rotation
Forward rotation
ON
ON
Stop
Reverse rotation
Stop
Forward
rotation start
Reverse
rotation start
STF
STR
SD
STP (STOP)
Inverter
Time
STF
STR
ON
ON
STP (STOP)
ON
OFF
OFF
Output frequency
Forward
rotation
Reverse
rotation
Time
Stop
Forward rotation
/reverse rotation
Start
STF
STR
ON
STP (STOP)
ON
STF
STR
SD
STP (STOP)
Inverter
ON
ON
OFF
OFF
Output frequency
Forward
rotation
Reverse
rotation