(E) Environment setting parameters
246
Disconnected PU detection (P.E101)
• When the inverter detects that the PU (operation panel/parameter unit) is disconnected from the inverter for 1 second or
more while
P.E101
or
Pr.75
is set to shut off the inverter output upon disconnection of the PU, the PU disconnection
("E.PUE") indication is displayed and the inverter output is shut off.
NOTE
• When the PU has been disconnected since before power-ON, the output is not shut off.
• To restart, confirm that the PU is connected and then reset.
• When the inverter detects that the PU is disconnected during PU JOG operation while
P.E101
or
Pr.75
is set to continue the
inverter operation even when the PU is disconnected, the inverter decelerates the motor to a stop.
• When RS-485 communication operation is performed through the PU connector, the reset selection/PU stop selection
function is valid but the disconnected PU detection function is invalid. (The communication is checked according to
Pr.122
PU communication check time interval
.)
PU stop selection (P.E102)
• Stop can be performed by inputting
from the PU in any of the operation modes of PU operation, External operation
and network operation.
• When stop is performed by the PU stop function, "
PS
" is displayed on the PU. A fault output is not provided.
• When
P.E102
="0" or
Pr.75
="0 to 3, 100 to 103" is set, deceleration stop using
is valid only in the PU operation
mode.
NOTE
• When
Pr.551 PU mode operation command source selection
="1" (PU mode RS-485 terminal), deceleration stop is
performed even when
is input during operation in PU mode via RS-485 communication.
How to restart after stopping with
input from the PU during External
operation (PU stop (PS) release method)
• PU stop release method for operation panel
1)
After completion of deceleration to a stop, switch OFF the STF and STR signal.
2)
Press
three times. (
PS
release)
(When
Pr.79 Operation mode selection
= "0 (initial value) or 6")
When
Pr.79
= "2, 3, or 7",
PU stop
can be released by pressing one time.
• PU stop release method for parameter unit
1)
After completion of deceleration to a stop, switch OFF the STF or STR signal.
2)
Press
. (
PS
release)
• The motor can be restarted by resetting the power supply or resetting with a RES signal.
NOTE
• Even when
Pr.250 Stop selection
"9999" is set and coasting stop is selected, deceleration stop and not coasting stop is
performed in the PU stop function during External operation.
EXT
Speed
Time
Key
Key
Stop/restart example for External operation
Operation
panel
STF ON
(STR) OFF