Inverter rating
673
8
FR-A860-00680 or higher
The applicable motor capacity indicated is the maximum capacity applicable for use of the 4-pole standard motor.
The rated output capacity indicated assumes that the output voltage is 575 V.
When an operation is performed with the carrier frequency set to 3 kHz or more, and the inverter output current reaches the value indicated in the parenthesis, the
carries frequency is automatically lowered. The motor noise becomes louder accordingly.
The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow time for the inverter
and motor to return to or below the temperatures under 100% load.
The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range. However, the maximum
point of the voltage waveform at the inverter output side is the power supply voltage multiplied by about
.
Value for the ND rating
The rated input current indicates a value at a rated output voltage. The impedance at the power supply side (including those of the input reactor and cables) affects the
rated input current.
The power supply capacity is the value when at the rated output current. It varies by the impedance at the power supply side (including those of the input reactor and
cables).
Model FR-A860-[ ]
00680
01080
01440
01670
02430
02890
03360
04420
Inverter capacity (kW)
37.0
55.0
75.0
90.0
110.0
132.0
185.0
220.0
Applicable motor
capacity (kW)
SLD
45
75
110
110
185
220
260
335
LD
45
75
90
110
150
185
220
300
ND (initial setting)
37
55
75
90
110
150
185
220
HD
30
45
55
75
90
110
150
185
Ou
tpu
t
Rated capacity
(kVA)
SLD
68
108
144
167
242
288
335
441
LD
62
99
131
152
221
254
303
401
ND (initial setting)
55
84
104
131
152
221
254
303
HD
41
63
84
104
131
152
202
254
Rated current (A)
SLD
68 (57.8)
108 (91.8)
144 (122)
167 (141)
243 (206)
289 (245)
336 (285)
442 (375)
LD
62 (52.7)
99 (84.1)
131 (111)
152 (129)
221 (187)
255 (216)
304 (258)
402 (341)
ND (initial setting)
55
84
104 (88)
131 (111)
152 (129)
221 (187)
255 (216)
304 (258)
HD
41
63
84 (71)
104 (88)
131 (111)
152 (129)
202 (171)
255 (216)
Overload current
rating
SLD
110% 60 s, 120% 3 s (inverse-time characteristics) at surrounding air temperature 40°C
LD
120% 60 s, 150% 3 s
(inverse-time
characteristics) at
surrounding air
temperature 40°C
120% 60 s, 150% 3 s (inverse-time characteristics) at surrounding air
temperature 50°C
ND (initial setting)
150% 60 s, 200% 3 s
(inverse-time
characteristics) at
surrounding air
temperature 40°C
150% 60 s, 200% 3 s (inverse-time characteristics) at surrounding air
temperature 50°C
HD
200% 60 s, 250% 3 s, 280% 0.5 s (inverse-time characteristics) at surrounding air temperature 40°C
Rated voltage
Three-phase 525 to 600 V
Regenerative
braking
Brake transistor
Built-in
Not included
Maximum brake torque
20% torque/continuous
―
―
―
―
―
―
Po
wer su
pply
Rated input
AC voltage/frequency
Three-phase 525 to 600 V 60 Hz
Permissible AC voltage fluctuation
472 to 660 V 60 Hz
Permissible frequency fluctuation
±5%
Rated input current
(A)
Without DC
reactor
SLD
87.0
―
―
―
―
―
―
―
LD
79.0
―
―
―
―
―
―
―
ND (initial setting)
70.5
108.0
―
―
―
―
―
―
HD
53.0
81.0
―
―
―
―
―
―
With DC
reactor
SLD
68.0 (57.8)
108.0 (91.8)
144.0 (122.0) 167.0 (141.0) 243.0 (206.0) 289.0 (245.0) 336.0 (285.0) 442.0 (375.0)
LD
62.0 (52.7)
99.0 (84.1)
131.0 (111.0) 152.0 (129.0) 221.0 (187.0) 255.0 (216.0) 304.0 (258.0) 402.0 (341.0)
ND (initial setting)
55.0
84.0
104.0 (88.0)
131.0 (111.0) 152.0 (129.0) 221.0 (187.0) 255.0 (216.0) 304.0 (258.0)
HD
41.0
63.0
84.0 (71.0)
104.0 (88.0)
131.0 (111.0) 152.0 (129.0) 202.0 (171.0) 255.0 (216.0)
Power supply
capacity (kVA)
Without DC
reactor
SLD
86.8
―
―
―
―
―
―
―
LD
79.1
―
―
―
―
―
―
―
ND (initial setting)
70.2
107.6
―
―
―
―
―
―
HD
52.3
80.7
―
―
―
―
―
―
With DC
reactor
SLD
68.0
108.0
144.0
167.0
242.0
288.0
335.0
441.0
LD
62.0
99.0
131.0
152.0
221.0
254.0
303.0
401.0
ND (initial setting)
55.0
84.0
104.0
131.0
152.0
221.0
254.0
303.0
HD
41.0
63.0
84.0
104.0
131.0
152.0
202.0
254.0
Protective structure (IEC 60529)
Open type (IP00)
Cooling system
Forced air
Approx. mass (kg)
36
41
52
52
55
112
115
153
Содержание 800 Series
Страница 11: ...MEMO 10 ...
Страница 17: ...MEMO 16 ...
Страница 95: ...MEMO 94 ...
Страница 671: ...MEMO 670 ...