(E) Environment setting parameters
264
Life display of the control circuit capacitor (Pr.257)
• The deterioration degree of the control circuit capacitor is displayed in
Pr.257
.
• In the operating status, the control circuit capacitor life is calculated from the energization time and temperature, and is
counted down from 100%. As soon as the control circuit capacitor life falls below 10%,
Pr.255
bit 0 is turned ON and also a
warning is output to the Y90 signal
Life display of the main circuit capacitor (Pr.258, Pr.259) (Standard
models)
POINT
POINT
• For accurate life measurement of the main circuit capacitor, wait three hours or longer after turning OFF. The temperature left
in the main circuit capacitor affects measurement.
• The deterioration degree of the main circuit capacitor is displayed in
Pr.258
.
• With the main circuit capacitor capacity at factory shipment as 100%, the capacitor life is displayed in
Pr.258
every time
measurement is made. When the measured value falls to 85% or lower,
Pr.255
bit 1 is turned ON and also a warning is
output to the Y90 signal.
• Measure the capacitor capacity according to the following procedure and check the deterioration degree of the capacitor
capacity.
1) Check that the motor is connected and at a stop.
2) Set "1" (measuring start) in
Pr.259
.
3) Switch the power OFF. The inverter applies DC voltage to the motor to measure the capacitor capacity while the
inverter is OFF.
4) After confirming that the power lamp is OFF, turn ON the power again.
5) Check that "3" (measurement complete) is set in
Pr.259
, read
Pr.258
, and check the deterioration degree of the main
circuit capacitor.
NOTE
• When the main circuit capacitor life is measured under the following conditions, "forced end" (
Pr.259
= "8"), or "measurement
error" (
Pr.259
= "9") may occur, or the status may remain in "measurement start" (
Pr.259
= "1"). To perform measurement,
first eliminate the following conditions. Under the following conditions, even if "measurement complete" (
Pr.259
= "3") is
reached, measurement cannot be performed correctly.
- Terminals R1/L11, S1/L21 or DC power supply is connected to terminals P/+ and N/-.
- The power supply is switched ON during measurement.
- The motor is not connected to the inverter.
- The motor is running (coasting).
- The motor capacity is smaller than the inverter capacity by two ranks or more.
- The inverter is tripped or a fault occurred while the power was OFF.
- The inverter output is shut off with the MRS signal.
- The start command is given while measuring.
- The applied motor setting is incorrect.
• Operation environment: surrounding air temperature (annual average of 40°C (free from corrosive gas, flammable gas, oil
mist, dust and dirt)).
Output current (80% of the inverter rating)
• Since repeated inrush currents at power ON will shorten the life of the converter circuit, frequent starts and stops of the
magnetic contactor must be avoided.
Pr.259
Description
REMARKS
0
No measurement
Initial value
1
Measurement start
Measurement starts when the power supply is switched OFF.
2
During measurement
Only displayed and cannot be set.
3
Measurement complete
8
Forced end
9
Measurement error
WARNING
When measuring the main circuit capacitor capacity (Pr.259 = "1"), the DC voltage is applied to the
motor for about 1 s at power OFF. Never touch the motor terminal, etc. right after powering OFF to
prevent an electric shock.