(M) Monitor display and monitor output signal
364
Calibration of terminal AM (Pr.901)
• Calibrate the AM terminal in the following procedure.
1) Connect a 0-10 VDC indicator (frequency meter) across terminals AM and 5 of the inverter. (Note the polarity. The
terminal AM is positive.)
2) Set a monitor item in
Pr.158 AM terminal function selection
. (Refer to
.)
When the output frequency or inverter output current is selected on the monitor, set the output frequency or current
value at which the output signal will be 10 V, using
Pr.55
or
Pr.56
beforehand.
3) If the meter needle does not point to maximum even at maximum output, calibrate it with
Pr.901
.
NOTE
• When outputting such an item as the output current, which cannot reach a 100% value easily by operation, set
Pr.158
to "21"
(reference voltage output) and calibrate. 10 VDC is output from the terminal AM.
• When
Pr.306 Analog output signal selection
= "21", the terminal AM calibration cannot be performed. For the details of
Pr.306
, refer to the Instruction Manual of FR-A8AY.
• Use
Pr.290
Monitor negative output selection
to enable negative output from the terminal AM. When this is set, the output
voltage range will be -10 VDC to +10 VDC. Calibrate the terminal AM with the maximum positive output value.
Adjusting the response of terminal AM (Pr.867)
• Using
Pr.867
, the output voltage response of the terminal AM can be adjusted in the range of 0 to 5 s.
• Increasing the setting stabilizes the terminal AM output more but reduces the response level. (Setting "0" sets the response
level to 7 ms.)
???????
Parameters referred to
Pr.54 FM terminal function selection
Pr.55 Frequency monitoring reference
Pr.56 Current monitoring reference
Pr.158 AM terminal function selection
Pr.290 Monitor negative output selection
Pr.291 Pulse train I/O selection
• Terminal AM is initially set to provide a 10 VDC output in the full-scale state
of the corresponding monitor item.
Pr.901
allows the output voltage ratio
(gains) to be adjusted according to the meter scale. Note that the
maximum output voltage is 10 VDC.
AM
Inverter
10VDC
5