(D) Operation command and frequency command
292
Operation mode basics
• The operation mode specifies the source of the start command and the frequency command for the inverter.
• Basically, there are following operation modes.
External operation mode
: For inputting a start command and a frequency command with an external potentiometer and
switches which are connected to the control circuit terminal.
PU operation mode
: For inputting a start command and a frequency command with the operation panel, parameter unit, or
RS-485 communication via the PU connector.
Network operation mode (NET operation mode)
: For inputting a start command and a frequency command using the
RS-485 terminals or communication option.
• The operation mode can be selected from the operation panel or with the communication instruction code.
NOTE
• There are two settings of "3" and "4" with PU/External combined operation. The startup method differs according to the
setting value.
• In the initial setting, the stop function (PU stop selection) by the operation panel or the parameter unit
is effective in
modes other than the PU operation mode. (Refer to
Pr.75 Reset selection/disconnected PU detection/PU stop
selectionon
1
2
3
4
5 6
7
8
9
10
Network operation
mode
Network operation mode
External operation mode
PU operation mode
Personal computer
Personal computer
Operation panel
Programmable controller
Potentiometer Switch
RS-485
terminals
Inverter
Communication
option
External terminal
Personal computer
USB
connector
USB
connector
USB
connector
PU connector
PU connector
PU connector
PU operation mode
Programmable controller
Personal computer